UFC 3-580-01-2007 TELECOMMUNICATIONS BUILDING CABLING SYSTEMS PLANNING AND DESIGN [Superseded NAVY MIL-HDBK-1012 3 CHG NOTICE 1 NAVY MIL-HDBK-1012 3]《电信大楼电缆系统的规划和设计[代替 NAVY MIL-HDB.pdf
《UFC 3-580-01-2007 TELECOMMUNICATIONS BUILDING CABLING SYSTEMS PLANNING AND DESIGN [Superseded NAVY MIL-HDBK-1012 3 CHG NOTICE 1 NAVY MIL-HDBK-1012 3]《电信大楼电缆系统的规划和设计[代替 NAVY MIL-HDB.pdf》由会员分享,可在线阅读,更多相关《UFC 3-580-01-2007 TELECOMMUNICATIONS BUILDING CABLING SYSTEMS PLANNING AND DESIGN [Superseded NAVY MIL-HDBK-1012 3 CHG NOTICE 1 NAVY MIL-HDBK-1012 3]《电信大楼电缆系统的规划和设计[代替 NAVY MIL-HDB.pdf(45页珍藏版)》请在麦多课文档分享上搜索。
1、UFC-3-580-01 22 June 2007 UNIFIED FACILITIES CRITERIA (UFC) TELECOMMUNICATIONS BUILDING CABLING SYSTEMS PLANNING AND DESIGN APPROVED FOR PUBLIC RELEASE; DISTRIBUTION UNLIMITED Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-UFC-3-580-01 22 June 2007
2、UNIFIED FACILITIES CRITERIA (UFC) TELECOMMUNICATIONS BUILDING CABLING SYSTEM PLANNING, DESIGN, AND ESTIMATING Any copyrighted material included in this UFC is identified at its point of use. Use of the copyrighted material apart from this UFC must have the permission of the copyright holder. U.S. AR
3、MY CORPS OF ENGINEERS (Preparing Activity) NAVAL FACILITIES ENGINEERING COMMAND AIR FORCE CIVIL ENGINEER SUPPORT AGENCY Record of Changes (changes indicated by 1 . /1/) Change No. Date Location This UFC supersedes MIL-HDBK-1012/3, dated MAY 1996. i Provided by IHSNot for ResaleNo reproduction or net
4、working permitted without license from IHS-,-,-UFC 3-580-01 22 June 2007 FOREWORD The Unified Facilities Criteria (UFC) system is prescribed by MIL-STD 3007 and provides planning, design, construction, sustainment, restoration, and modernization criteria, and applies to the Military Departments, the
5、 Defense Agencies, and the DoD Field Activities in accordance with USD(AT also assume that there will be no diversification of this load. For Navy projects, utilize 4-inch (102 mm) square by 2-1/4 inch (57 mm) deep boxes for single gang, four outlet copper telecommunications configurations that do n
6、ot have provision for fiber optic cabling. For Army projects, specify 4-11/16-inch (119 mm) square by 2-1/4 (57 mm) boxes for 1-inch (27 mm) conduit installations and outlet boxes that have or may require fiber optic cabling. 2-3.2 Outlet Faceplate Use a full (double gang) faceplate for standard adm
7、inistrative outlet locations, with connectors for all copper and (if used) fiber optic cable. Standard administrative outlets may, by specific user request, use single gang outlet faceplates in conjunction with a reducing ring. For single gang outlet boxes, use a single gang outlet faceplate with ap
8、propriate connector locations and, if required, mounting lugs for wall phones. Outlet faceplate must include two blanks position for future applications. 2-3.3 Outlet Connectors The following specifications pertain to copper, fiber optic and coaxial cable outlet/connector. The category for cable, ja
9、cks, termination blocks, and patch panels must be the same throughout each circuit and system. Specify more than one category only if providing more than one system requiring different categories. In general for horizontal cable, use Category 6 for all voice and data circuits on Army and Navy projec
10、ts, and use Cat 5 or better for USAF projects. 2-3.3.1 Copper Outlet/connector Copper outlet/connector must be TIA/EIA category 6 (Cat 6) for Army and Navy projects, and Cat 5 or better for USAF projects All connectors must be 8-pin/8-position Provided by IHSNot for ResaleNo reproduction or networki
11、ng permitted without license from IHS-,-,-UFC-3-580-01 22 June 2007 6 insulation displacement terminations wired per T568A. The T568B configuration must only be used by exception if required to maintain system configuration uniformity, security or other user-specified reasons. Category 3 (Cat 3) rat
12、ed connectors must not be used in new construction, or rehabilitation projects. Copper outlet/connector and plugs should be unkeyed unless the user requires keyed outlet/connector and plugs to maintain system uniformity, security, or other user specified reasons. 2-3.3.2 Fiber Optic Outlet/connector
13、 Terminate all fiber optic work area cables in dual 568SC connectors. Provide fiber optic connectors in accordance with the paragraph entitled “Fiber Optic Terminations” in this UFC. The default choice for fiber optic outlet/connector must be TIA/EIA “SC” type (568SC). Other type connectors (small-f
14、orm-factor) (MT-RJ, VF-45, etc.) may be substituted as required by the user. Small form factor connectors (available from several manufacturers), offer a potential for significant installation cost reduction. Any type of fiber connector used must meet the performance requirements specified within An
15、nex A of TIA/EIA-568-B.3, and meet the requirements of the corresponding TIA Fiber Optic Connector Intermateability Standard (FOCIS) document. 2-3.3.3 Coaxial Outlet/connector Coaxial outlet/connector should normally be “F” type connectors. Use of other type connectors (i.e., BNC, etc.) should be co
16、nsidered only if specifically required by the user. The designer must coordinate with the cable service provider where franchise agreements are in place. The Navy requires that all passive CATV devices support 1 GHz bandwidth. 2-3.4 Outlet/Connector Markings Each communications outlet must have a un
17、ique identifying number in accordance with TIA/EIA 606-A. In the telecommunications room (TR), this unique identifying number must be associated with the position on the patch panel or cross-connect to which the outlet is connected. Each horizontal cable must be labeled both at the outlet and patch
18、panel or cross-connect position in the communications closet. Connector voice and data dedication use may be reassigned as requirements dictate. Note: in the standard cabling scheme, the designations “voice” and “data” are arbitrary and do not imply that one outlet is better than the other, the outl
19、ets are identical in capability. 2-3.5 Outlet Types and Density The following outlet types are commonly used in military construction projects. Sketches of these outlets are included in Figure 6, of Appendix B. The outlet types do not cover all possible user required configurations. The designer mus
20、t certify that all user-defined outlets have a corresponding valid requirement, such as fiber for various levels of classification. Outlet configurations must comply with this UFC, TIA/EIA-568-B, and TIA/EIA-569-B. Outlet densities are provided for planning purposes, when actual outlet locations are
21、 not known and cannot be determined with available information. The designer can develop reasonably accurate total outlet count estimates based on the size and dedicated usage of the space. These factors fall within the ranges given in TIA/EIA-569-B, and are based on gross area (overall building foo
22、tprint without deducting for hallways, equipment rooms, restrooms, etc.). See Figure 9, of Appendix Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-UFC-3-580-01 22 June 2007 7 B, for a typical building floor plan. For USAF projects all administrative
23、 facilities and administrative spaces in other types of facilities must be equipped with one standard telecommunications outlet for each 48 square feet (4.5 square meters) of net office space. Outlet densities and locations for all special-purpose spaces and non-administrative facilities must be det
24、ermined by the user and the BCSO and must follow the guidelines in TIA/EIA-569-B. Table 2-1 Outlet Types Facility Space Category Outlet Configuration Planning Area (SF(SM) per Outlet Administrative space, to include Classrooms, and Medical/Clinics Two 8-pin modular (RJ45 type) outlet/connector in a
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- UFC3580012007TELECOMMUNICATIONSBUILDINGCABLINGSYSTEMSPLANNINGANDDESIGNSUPERSEDEDNAVYMILHDBK10123CHGNOTICE1NAVYMILHDBK10123

链接地址:http://www.mydoc123.com/p-1066947.html