UFC 3-520-05-2008 STATIONARY BATTERY AREAS《固定式电池区》.pdf
《UFC 3-520-05-2008 STATIONARY BATTERY AREAS《固定式电池区》.pdf》由会员分享,可在线阅读,更多相关《UFC 3-520-05-2008 STATIONARY BATTERY AREAS《固定式电池区》.pdf(21页珍藏版)》请在麦多课文档分享上搜索。
1、UFC 3-520-05 April 14, 2008 UNIFIED FACILITIES CRITERIA (UFC) STATIONARY BATTERY AREAS APPROVED FOR PUBLIC RELEASE: DISTRIBUTION UNLIMITED Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-UFC 3-520-05 April 14, 2008 STATIONARY BATTERY AREAS Any copyri
2、ghted material included in this UFC is identified at the point of use. Use of the copyrighted material apart from this UFC must have the permission of the copyright holder. NAVAL FACILITIES ENGINEERING COMMAND (Preparing Activity) U.S. ARMY CORPS OF ENGINEERS AIR FORCE CIVIL ENGINEER SUPPORT AGENCY
3、Record of Changes (changes are indicated by 1 . /1/) Change No. Date Location Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-UFC 3-520-05 April 14, 2008 FOREWORD The Unified Facilities Criteria (UFC) system is prescribed by MIL-STD 3007 and provides
4、 planning, design, construction, sustainment, restoration, and modernization criteria, and applies to the Military Departments, the Defense Agencies, and the DoD Field Activities in accordance with USD(AT design a separate space for these materials. 2-2.3 Provide battery enclosures that are a commer
5、cial manufactured product, designed and UL listed for battery containment. Provide a minimum 200 mm (8 in.) working clearance around the batteries within the enclosure. For outside installations prevent entry of contaminants, water, insects, and wildlife. 2-2.4 Provide spill control for battery inst
6、allations as required by NFPA 1. An electrolyte spill is defined as an unintended release of liquid electrolyte that exceeds 1.0 liters. Battery enclosures that do not provide integral spill containment shall not be used. Permanently installed physical containment structures shall be capable of resi
7、sting continuous exposure to a 70 percent concentration of the electrolytes acid or alkaline chemical. The containment area shall not encroach upon space designated for room egress. Note: Valve-regulated lead acid (VRLA) batteries have the electrolyte immobilized in a gel or absorbent glass mats. Th
8、e immobilization limits the potential release of electrolyte to much less than the definition of a spill. For this reason, VRLA designs do not require permanently installed spill containment systems. Electrolyte releases from Provided by IHSNot for ResaleNo reproduction or networking permitted witho
9、ut license from IHS-,-,-UFC 3-520-05 April 14, 2008 4 VRLA batteries, while small, can occur and the necessary supplies for manual cleanup should be available in the battery area. 2-2.5 Provide for spilled electrolyte neutralization in accordance with NFPA 1. Provide neutralizing and absorbing mater
10、ials local to, but outside of, the battery area to address local incidents. 2-2.6 Floor finish in all battery rooms and enclosures shall be slip-resistant and acid or alkali resistant as appropriate for the battery chemistry employed. Wall and ceiling finishes in vented (flooded) cell installations
11、shall be acid or alkali resistant. 2-2.7 Obtain the battery rack from the same manufacturer that supplies the battery. Racks and trays shall resist corrosion from continuous exposure to a 70 percent concentration of the electrolytes acid or base chemical. Battery lifting devices shall be insulated a
12、nd tools shall be provided with insulated handles. 2-2.7.1 Select the battery rack to fit within the defined footprint while also satisfying the need for maintenance access. Figures 2-1 and 2-2 show acceptable battery rack configurations for vented cells. Figure 2-1. Two-Step Battery Rack Configurat
13、ions (End View) CellCella. Two-tier batteryCellCellb. Two-step batteryMust Be Open in Front of Rack to Provide AccessProvided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-UFC 3-520-05 April 14, 2008 5 Figure 2-2. Larger Battery Rack Configurations (End Vie
14、w) CellCellCella. Three-step batteryCellCellCellCellb. Two-tier, two-step batteryMust Be Open in Front of Rack to Provide AccessMust Provide Clearance Behind Rack for Access2-2.7.2 All racks for vented cell installations shall provide restraints to prevent the individual cells from overturning. In a
15、ddition, battery racks shall comply with the latest edition of ASCE/SEI 7-05. Table 2-1 shows the rack requirements based on seismic design category. Table 2-1. Battery Rack Requirements by Seismic Design Category Seismic Design Category Description Aearthquakes are unlikely. Racks do not require ce
16、ll restraints. Bdistant earthquakes might cause minor motion. Racks require side restraints. C, D, E, Flocal or nearby earthquake. Racks require heavy-duty construction with side restraints and should have additional floor anchor points. 2-2.8 Batteries with a nominal voltage above 250 volts require
17、 special installation considerations as detailed in NFPA 70 Article 480.7 (2008 Edition). 2-2.9 Provide an overhead hoist or equivalent portable material handling equipment for the handling of batteries. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-
18、,-UFC 3-520-05 April 14, 2008 6 2-3 MECHANICAL REQUIREMENTS. 2-3.1 Design mechanical systems to maintain ventilation rates in accordance with NFPA 70E. Areas designated as a battery room shall be mechanically ventilated. Areas designated as battery enclosures shall be ventilated as required by the s
19、ystem manufacturer to meet the applicable codes. 2-3.2 Installation, operating, and maintenance requirements vary for each battery type. Refer to UFC 3-520-01 for battery selection guidance. Note: Gelled electrolyte (Gel-cell) batteries and absorbed electrolyte batteries are both types of valve-regu
20、lated lead acid (VRLA) batteries, and have been inappropriately referred to as sealed maintenance-free batteries. Although the cell modules are sealed, making it incapable of water addition to the cells, each cell is equipped with a vent, which opens periodically to release internal pressure. The ve
21、nt is typically open only for a fraction of a second, permitting small amounts of gas to escape. NFPA 70E and IEEE 1187 specify that VRLA cells be treated with the same hydrogen control measures as vented lead acid cells. 2-3.3 Comply with the following IEEE documents for temperature control criteri
22、a, as appropriate for the selected battery type: IEEE Std 484-2002, IEEE Recommended Practice for Installation Design and Installation of Vented Lead acid Batteries for Stationary Applications. IEEE Std 1106-2005, IEEE Recommended Practice for Installation, Maintenance, Testing, and Replacement of V
23、ented Nickel-Cadmium Batteries for Stationary Applications. IEEE Std 1187-2002, IEEE Recommended Practice for Installation Design and Installation of Valve-Regulated Lead acid Storage Batteries for Stationary Applications. Evaluate temperature conditions, and provide heating and ventilation as neces
24、sary to maintain temperature within the range 60 F (17 C) and 90 F (32 C). Base requirements on weather data obtained from UFC 3-400-02, Design: Engineering Weather Data. Air conditioning is not authorized. However, extended periods of high temperatures can reduce battery life; in those climates whe
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- UFC3520052008STATIONARYBATTERYAREAS 固定 电池 PDF

链接地址:http://www.mydoc123.com/p-1066944.html