REG UFGS-21 22 00 00 40-2013 CLEAN AGENT FIRE EXTINGUISHING SYSTEMS.pdf
《REG UFGS-21 22 00 00 40-2013 CLEAN AGENT FIRE EXTINGUISHING SYSTEMS.pdf》由会员分享,可在线阅读,更多相关《REG UFGS-21 22 00 00 40-2013 CLEAN AGENT FIRE EXTINGUISHING SYSTEMS.pdf(22页珍藏版)》请在麦多课文档分享上搜索。
1、*USACE / NAVFAC / AFCESA / NASA UFGS-21 22 00.00 40 (May 2013)-Preparing Activity: NASA SupersedingUFGS-21 22 00.00 40 (May 2010)UNIFIED FACILITIES GUIDE SPECIFICATIONSReferences are in agreement with UMRL dated April 2013*SECTION TABLE OF CONTENTSDIVISION 21 - FIRE SUPPRESSIONSECTION 21 22 00.00 40
2、CLEAN AGENT FIRE EXTINGUISHING SYSTEMS05/13PART 1 GENERAL1.1 REFERENCES1.2 SYSTEM DESCRIPTION1.2.1 Design Requirements1.2.1.1 System Layout1.2.1.2 Mandatory System Approvals1.2.2 Performance Requirements1.3 SUBMITTALS1.4 PREDICTIVE TESTING AND INSPECTION TECHNOLOGY REQUIREMENTS1.5 QUALITY ASSURANCE1
3、.5.1 Previous Product Installation1.5.2 Installation Drawings1.5.3 Calculations1.5.4 Record Drawings1.6 SPECIAL HAZARDS SUPPRESSION SYSTEMSPART 2 PRODUCTS2.1 EQUIPMENT2.2 COMPONENTS2.2.1 Piping2.2.1.1 Pipe Hangers And Supports2.2.1.2 Pipe Sleeves2.2.2 Escutcheons2.3 SUPERVISORY SWITCH2.3.1 Low Press
4、ure Alarm Switch2.4 CONTROL PANEL2.4.1 Secondary Power Supply2.4.1.1 Storage Batteries2.4.1.2 Battery Charger2.5 MANUAL ACTUATION STATIONS2.6 SMOKE DETECTORS2.6.1 Ionization Detectors2.6.2 Photoelectric Detectors2.6.3 Detector Spacing and LocationSECTION 21 22 00.00 40 Page 1Provided by IHSNot for R
5、esaleNo reproduction or networking permitted without license from IHS-,-,-2.7 INHIBIT SWITCH2.8 ALARM SIGNALING DEVICES2.8.1 Audible Alarms2.8.2 Visual Alarms2.9 MAIN ANNUNCIATOR2.9.1 Annunciation Zones2.9.2 Annunciator Panels2.10 AUTOMATIC FIRE DAMPERS2.11 ELECTROMAGNETIC DOOR HOLDER RELEASE2.12 EL
6、ECTRICAL WORK2.12.1 Wiring2.12.2 Operating Power2.12.3 Conductor IdentificationPART 3 EXECUTION3.1 INSTALLATION3.1.1 Warning Signs3.1.1.1 Inside Control Room3.1.1.2 Protected Space3.1.1.3 Manual Activation or Release Station3.1.2 System Control3.1.2.1 Controls3.1.2.2 Suppression System Saving/Discon
7、nect Switch3.1.3 Electrical Work3.1.4 Operating Instructions3.1.5 Field Painting3.2 FIELD QUALITY CONTROL3.2.1 Test Procedure3.2.2 Preliminary Tests3.2.3 Formal Tests3.2.4 Manufacturers Representative- End of Section Table of Contents -SECTION 21 22 00.00 40 Page 2Provided by IHSNot for ResaleNo rep
8、roduction or networking permitted without license from IHS-,-,-*USACE / NAVFAC / AFCESA / NASA UFGS-21 22 00.00 40 (May 2013)-Preparing Activity: NASA SupersedingUFGS-21 22 00.00 40 (May 2010)UNIFIED FACILITIES GUIDE SPECIFICATIONSReferences are in agreement with UMRL dated April 2013*SECTION 21 22
9、00.00 40CLEAN AGENT FIRE EXTINGUISHING SYSTEMS05/13*NOTE: This guide specification covers the requirements for clean agent fire extinguishing systems.Adhere to UFC 1-300-02 Unified Facilities Guide Specifications (UFGS) Format Standard when editing this guide specification or preparing new project s
10、pecification sections. Edit this guide specification for project specific requirements by adding, deleting, or revising text. For bracketed items, choose applicable items(s) or insert appropriate information.Remove information and requirements not required in respective project, whether or not brack
11、ets are present.Comments, suggestions and recommended changes for this guide specification are welcome and should be submitted as a Criteria Change Request (CCR).*PART 1 GENERAL*NOTE: Edit this specification section as either a performance-designed system or a fully designed system as applicable.(1)
12、 Highlight all concealed spaces on the drawings that require protection, such as spaces above suspended ceilings.A fully designed system includes the items listed above and all additional information required that is required by NFPA 2001 for a fully operational system.Select the appropriate Divisio
13、n 28 Fire Detection and Alarm section to address the project requirements.SECTION 21 22 00.00 40 Page 3Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-*1.1 REFERENCES*NOTE: This paragraph is used to list the publications cited in the text of the guid
14、e specification. The publications are referred to in the text by basic designation only and listed in this paragraph by organization, designation, date, and title.Use the Reference Wizards Check Reference feature when you add a RID outside of the Sections Reference Article to automatically place the
15、 reference in the Reference Article. Also use the Reference Wizards Check Reference feature to update the issue dates.References not used in the text are automatically deleted from this section of the project specification when you choose to reconcile references in the publish print process.*The pub
16、lications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.ASTM INTERNATIONAL (ASTM)ASTM A53/A53M (2012) Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamle
17、ssASTM B88 (2009) Standard Specification for Seamless Copper Water TubeMANUFACTURERS STANDARDIZATION SOCIETY OF THE VALVE AND FITTINGS INDUSTRY (MSS)MSS SP-58 (2009) Pipe Hangers and Supports - Materials, Design and Manufacture, Selection, Application, and InstallationNATIONAL AERONAUTICS AND SPACE
18、ADMINISTRATION (NASA)NASA-STD-5008A (2011b) Protective Coating of Carbon Steel, Stainless Steel, and Aluminum on Launch Structures, Facilities, and Ground Support EquipmentRCBEA GUIDE (2004) NASA Reliability Centered Building and Equipment Acceptance GuideNATIONAL FIRE PROTECTION ASSOCIATION (NFPA)N
19、FPA 101 (2012; Amendment 1 2012) Life Safety CodeSECTION 21 22 00.00 40 Page 4Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-NFPA 2001 (2012; AMD 1 2012) Standard on Clean Agent Fire Extinguishing SystemsNFPA 70 (2011; Errata 2 2012) National Electr
20、ical CodeNFPA 72 (2013) National Fire Alarm and Signaling CodeU.S. GENERAL SERVICES ADMINISTRATION (GSA)FED-STD-595 (Rev C; Notice 1) Colors Used in Government ProcurementUNDERWRITERS LABORATORIES (UL)UL 2127 (2012) Inert Gas Clean Agent Extinguishing System UnitsUL 2166 (2012) Halocarbon Clean Agen
21、t Extinguishing System UnitsUL 536 (1997; Reprint Jun 2003) Flexible Metallic Hose1.2 SYSTEM DESCRIPTION1.2.1 Design RequirementsSubmit Installation Drawings for Clean Agent Fire Protection Systems in accordance with the requirements of NFPA 2001. Include details of equipment layout and design. Indi
22、cate the general physical layout of all controls, manual actuation stations, and internal tubing and wiring details. Provide electronic drawings in Microstation.dgn format or AutoCAD.dwg format. If the electronic files are AutoCAD format, only use standard AutoCAD fonts and line styles and furnish t
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- REGUFGS21220000402013CLEANAGENTFIREEXTINGUISHINGSYSTEMSPDF

链接地址:http://www.mydoc123.com/p-1019641.html