1、Public Lessons Learned Entry: 6396 Lesson Info: Lesson Number: 6396 Lesson Date: 2011-2-1 Submitting Organization: JPL Submitted by: David Oberhettinger Subject: An Electrical Outage Revealed Emergency Systems Not Functioning as Expected Abstract: JPL experienced a total electrical power loss in Jun
2、e 2010 due to an operator error at a public utility substation. Deficiencies were noted in the emergency response and notifications, and in the operation of emergency generators and emergency lighting. Process changes are needed to address the significant potential impacts of these deficiencies on p
3、ersonnel, flight assets, and JPL activities. Description of Driving Event: On June 25, 2010, at 7:38 pm, the NASA/Caltech Jet Propulsion Laboratory (JPL) experienced a total electrical power loss due to an operator error at a public utility substation that de-energized the 66kv operating bus (Refere
4、nce (1). The supplied power for the entire JPL Oak Grove campus was unavailable for approximately 3 minutes. The Lab-wide power outage was categorized as a Class D mishap because it impacted the safety of both personnel and flight assets, including: An employee was stranded in an elevator for approx
5、imately 1 hour, 55 minutes, until JPL Protective Services forcibly opened the elevator doors with emergency extraction equipment. This was a new building, and the JPL Fire Department did not have a key to this elevator due to the requirements of a maintenance and response contract with the elevator
6、vendor. In several buildings, emergency lights, emergency generators, and/or uninterruptable power supplies (UPSs) did not function as designed or planned. The affected buildings included mission-critical facilities currently engaged in testing spaceflight hardware. The failures were related to: o U
7、nreliable generators, o Insufficient generator capacity, o A defective relay and an improperly programmed switch for automatic switchover to generator power, o A tripped UPS circuit breaker, o Emergency lighting fixtures that had been removing during remodeling, o Inoperable emergency lighting inver
8、ters, o Emergency lighting inadequate to illuminate the egress path, and o Insufficient capacity of an auxiliary air conditioning system. The procedures for timely incident reporting to JPL executive management were inadequate. Because the personnel list used for notifications by the Critical Hardwa
9、re and Proximate Hazard System (CHAPHS) did not include JPL senior management, the JPL Deputy Director was not notified of the incident until the next morning. The incident caused no personnel injury or illness, and damage was limited to the estimated $16,000 cost for repair to the elevator (Figure
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- REGNASALLIS63962012LESSONSLEARNEDANELECTRICALOUTAGEREVEALEDEMERGENCYSYSTEMSNOTFUNCTIONINGASEXPECTEDPDF

链接地址:http://www.mydoc123.com/p-1019536.html