1、NFPA 25 2017 Edition Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems TIA Log No.: 1287 Reference: Various sections Comment Closing Date: October 19, 2017 Submitter: Tracey Bellamy, Telgian Corporation 1. Add NFPA 70E, Standard for Electrical Safety in the
2、 Workplace, 2015 edition to section 2.2. 2. Revise 4.9.6 and associated Annex A material to read as follows: 4.9.6* Electrical Safety. 4.9.6.1 Legally required precautions shall be taken when testing and maintaining electric controllers for motor-driven fire pumps. 4.9.6.2 At a minimum, the provisio
3、ns of NFPA 70E shall be applied. A.4.9.6 WARNING: NFPA 20 includes electrical requirements that discourage the installation of a disconnect means and limit overcurrent protection in the power supply to electric motordriven fire pumps. This is intended to ensure the availability of power to the fire
4、pumps. Where equipment connected to those circuits is serviced or maintained, the service person could be subject to unusual exposure to electrical and other hazards. It could be necessary to establish special safe work practices and to use safeguards or personal protective clothing, or both. The re
5、quired category of personal protective equipment will vary dependent upon the specific installation details and associated incident energy levels. The determination of such incident energy levels can be established by conducting an incident energy level analysis as provided in Annex D of NFPA 70E or
6、 by utilization of the PPE Category Method provided by NFPA 70E, Table 130.7(C)(15)(A)(b), where applicable. Use of the PPE Category Method requires that the maximum available short-circuit current and maximum fault clearing time for the actual installation do not exceed those indicated in NFPA 70E,
7、 Table 130.7(C)(15)(A)(b). See also NFPA 70E for additional safety guidance regarding the determination of the incident energy and the required level of personal protective equipment. The provisions of NFPA 70E require that the owner label the equipment with information regarding the electrical haza
8、rds associated with the installation. Where such labeling is not present, the technician cannot make a determination for safe work practice on the equipment without further assessment of the incident energy associated with the installation. 3. Revise sections in 8.1.1.2 to read as follows: 8.1.1.2.2
9、 Electrical connections shall be checked annually and repaired as necessary to the extent that such work can be completed without opening an energized electric motordriven fire pump controller. 8.1.1.2.4 Printed circuit boards (PCBs) shall be checked annually for corrosion to the extent that such wo
10、rk can be completed without opening an energized electric motordriven fire pump controller. 8.1.1.2.5 Cable and/or wire insulation shall be checked annually for cracking to the extent that such work can be completed without opening an energized electric motordriven fire pump controller. 8.1.1.2.6 Pl
11、umbing parts, both inside and outside of electrical panels, shall be checked annually for any leaks to the extent that such work can be completed without opening an energized electric motordriven fire pump controller. 8.1.1.2.12 Engine crankcase breathers shall be checked quarterly annually. 8.1.1.2
12、.16 All controls and power wiring connections shall be checked annually and repaired as necessary to the extent that such work can be completed without opening an energized electric motordriven fire pump controller. 8.1.1.2.21 The accuracy of pressure gauges and sensors shall be inspected annually a
13、nd replaced or recalibrated when more than 5 percent out of calibration to the extent that such work can be completed without opening an energized electric motordriven fire pump controller. 4. Revise Table 8.1.1.2 to read as follows: Table 8.1.1.2 Summary of Fire Pump Inspection, Testing, and Mainte
14、nance Item Frequency Reference Inspection Alignment Annually 8.3.6.4Cable/wire insulation Annually 8.1.1.2.5Diesel pump system Weekly 8.2.2(4) Electric pump system Weekly 8.2.2(3) Engine crankcase breather Annually 8.1.1.2.12 Exhaust system and drain condensate trap Annually 8.1.1.2.13 Flexible hose
15、s and connections Annually 8.1.1.2.11 Fuel tank vents and overflow Annually 8.1.1.2.10 Plumbing parts inside and outside of panels Annually 8.1.1.2.6 Printed circuit board corrosion (PCBs) Annually 8.1.1.2.4 Pump Weekly 8.2.2(2) Pump house/room Weekly 8.2.2(1) Shaft movement or endplay while running
16、 Annually 8.1.1.2.1 Steam pump system Weekly 8.2.2(5) Suction screens Annually 8.3.3.712 Test Automatic transfer switch and emergency/standby generators Per NFPA 110 8.3.6.1 and 8.3.6.2 Diesel enginedriven fire pump Weekly 8.3.1.1 Diesel fuel testing Annually/Semiannually 8.3.4 Electric motordriven
17、fire pump Weekly/monthly 8.3.1.2Electronic control module (ECM) Annually 8.3.3.13 Fire pump alarm signals Annually 8.3.3.510 Fuel tank, float switch, and supervisory signal for interstitial space Quarterly 8.1.1.2.7 Main relief valve Annually 8.3.3.38 Power transfer switch Annually 8.3.3.49 Pump hou
18、seroom environmental conditions 8.3.6.3 Item Frequency Reference Pump operation (no flow) Weekly/monthly 8.3.1 Pump performance (flow) Annually 8.3.3 Supervisory signal for high cooling water temperature Annually 8.1.1.2.8 Maintenance Batteries Annually 8.1.1.2.15Circulating water filter Annually 8.
19、1.1.2.20Control and power wiring connections Annually 8.1.1.2 16 Controller Per manufacturer 8.5 Diesel active fuel maintenance system Annually or per manufacturer recommendation 8.3.4.3 Diesel engine system Per manufacturer 8.5 Electric motor and power system Per manufacturer 8.5 Electrical connect
20、ions Annually 8.1.1.2.2 Engine lubricating oil Annually or 50 operating hours 8.1.1.2.17 Engine oil filter Annually or 50 operating hours 8.1.1.2.18 Fuel tank check for water and foreign materials Annually 8.1.1.2.9 Measure back pressure on engine turbo Annually 8.1.1.2.14 Pressure gauges and sensor
21、s Annually 8.1.1.2.21Pump and motor bearings and coupling Annually or as required 8.51.1.2.3 Sacrificial anode Annually 8.1.1.2.19 5. Revise the Electrical System section of Table A.8.1.1.2 for the following line items to read as follows: Tighten electrical connections as necessary X Annually Calibr
22、ate pressure switch settings* X Annually Voltmeter and ammeter for accuracy (5%) X Annually Any corrosion on printed circuit boards (PCBs)*X Annually Any cracked cable/wire insulation* X Annually Any leaks in plumbing parts* X Annually Any signs of water on electrical parts* X Annually * Required on
23、ly where the extent of such work can be completed without the opening of an energized electric motordriven fire pump controller. 6. Revise 8.3.2.8(2) to read as follows: 8.3.2.8 The pertinent visual observations or adjustments specified in the following checklists shall be conducted while the pump i
24、s idle: (1) Record the system suction and discharge pressure gauge readings. (2) For pumps that use electronic pressure sensors to control the fire pump operation, record the current pressure and the highest and the lowest pressure shown on the fire pump controller event log where such information i
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NFPA25AMD2017ENSTANDARDFORTHEINSPECTIONTESTINGANDMAINTENANCEOFWATERBASEDFIREPROTECTIONSYSTEMSPDF

链接地址:http://www.mydoc123.com/p-1008503.html