1、 AEROSPACE STANDARD CABLE, POWER, ELECTRICAL, 600 VOLTS, PORTABLE, MULTICONDUCTOR AS5756/3 Copyright 2016 SAE International All rights reserved. No part of this publication may be reproduced, stored in a retrieval system or transmitted, in any form or by any means, electronic, mechanical, photocopyi
2、ng, recording, or otherwise, without the prior written permission of SAE. TO PLACE A DOCUMENT ORDER: Tel: 877-606-7323 (inside USA and Canada) Tel: +1 724-776-4970 (outside USA) Fax: 724-776-0790 Email: CustomerServicesae.org SAE WEB ADDRESS: http:/www.sae.org ISSUED2004-06REVISED2010-10REAFFIRMED 2
3、016-05THIRD ANGLE PROJECTION CUSTODIAN: AE-8/AE-8D REV.A FEDERAL SUPPLY CLASS 6145 AS5756/3 SHEET 1 OF 4 REV. A PROCUREMENT SPECIFICATION: AS5756 SAE Technical Standards BoardRules providethat:“This reportis publishedby SAE to advance thestateoftechnical andengineering sciences. The useofthis report
4、is entirely voluntary, and its applicability and suitability forany particularuse, includingany patent infringement arising therefrom, is thesole responsibility of theuser.” SAE reviews eachtechnical reportatleastevery five years at whichtime it may berevised, reaffirmed, stabilized, or cancelled. S
5、AEinvites your written comments and suggestions. SAE values your input. To provide feedback on this Technical Report, please visit http:/www.sae.org/technical/standards/AS5756/3A RATIONALE AS5756/3A HAS BEEN REAFFIRMED TO COMPLY WITH THE SAE FIVE-YEAR REVIEW POLICY. THE REQUIREMENTS FOR PROCURING TH
6、E CONTACTS DESCRIBED HEREIN SHALL CONSIST OF THIS SPECIFICATION AND THE LATEST ISSUE OF: SAE AS5756 FIGURE 1 EXAMPLE OF 3 CONDUCTOR CABLE REQUIREMENTS: QUALIFICATION REQUIRED. CONSTRUCTION (SEE TABLE 1) FIRST - COPPER CONDUCTOR, SEE TABLE I OF AS5756 FOR REQUIREMENTS, SIZES 10 AWG AND SMALLER SHALL
7、BE TIN-COATED, SIZES 8 AWG AND LARGER SHALL BE UNCOATED. SECOND - SEPARATOR, REQUIRED WHERE UNCOATED CONDUCTORS ARE USED, OPTIONAL WHERE TIN-COATED CONDUCTORS ARE USED. THIRD - INSULATION OF SYNTHETIC OR NATURAL RUBBER (SEE TABLE I FOR THICKNESS), COLOR CODED PER PARAGRAPH 3.4.6 OF AS5756. FOURTH -
8、THE REQUIRED NUMBER OF CONDUCTORS CABLED TOGETHER WITH A LEFT-HAND LAY NOT GREATER THAN 16 TIMES THE DIAMETER UNDER THE JACKET. WHEN NEEDED, FILLERS SHALL BE EMPLOYED TO OBTAIN A FIRM, WELL-ROUNDED ASSEMBLY. FIFTH - BINDER TAPE APPLIED HELICALLY WITH OVERLAP. SIXTH - NATURAL OR SYNTHETIC RUBBER JACK
9、ET (SEE TABLE I FOR THICKNESS). CABLE SURFACE MARKING REQUIRED. OZONE RESISTANCE - REQUIRED. NOTICE AEROSPACE STANDARD AS5756/3 SHEET 2 OF 4 REV. A CABLE, POWER, ELECTRICAL, 600 VOLTS, PORTABLE, MULTICONDUCTOR TABLE 1 DETAILS OF CONSTRUCTION PART NO. M5756/3 CONDUCTOR SIZE NUMBER OF CONDUCTORS NOMIN
10、AL INSULATIONTHICKNESS(INCH) 1/ NOMINAL JACKET THICKNESS(INCH) 2/ OVERALL DIAMETER OF JACKETED CABLECONDUCTOR RESISTANCE PER 1000 FEET (MAX) 20C (OHMS) NOMINAL WEIGHT PER1000 FEET (POUNDS) 3/ MIN (INCHES) MAX (INCHES) -001 18 2 .031 .0625 .316 .375 7.49 60.9 -002 16 2 .031 .0625 .338 .399 4.70 72.5
11、-003 14 2 .047 .078 .429 .530 2.96 127.9 -004 12 2 .047 .078 .499 .576 1.86 159.3 -005 10 2 .047 .094 .549 .648 1.20 217.7 -006 8 2 .063 .109 .705 .824 .699 335.0 -007 6 2 .063 .125 .831 .962 .444 487.2 -008 4 2 .063 .141 .965 1.100 .279 676.9 -009 2 2 .063 .156 1.150 1.270 .177 945.1 -010 1 2 .078
12、.156 1.270 1.410 .141 1173.1 -011 1/0 2 .078 .172 1.360 1.540 .111 1422.5 -012 2/0 2 .078 .187 1.560 1.740 .0893 1780.0 -013 3/0 2 .078 .187 1.710 1.890 .0708 2131.3 -014 4/0 2 .078 .203 1.840 2.050 .0562 2586.6 -015 250 2 .094 .203 2.010 2.220 .0476 3045.2 -016 18 3 .031 .0625 .331 .392 7.49 71.9 -
13、017 16 3 .031 .0625 .356 .418 4.70 87.2 -018 14 3 .047 .078 .482 .557 2.96 154.0 -019 12 3 .047 .094 .527 .606 1.86 213.9 -020 10 3 .047 .094 .611 .692 1.20 268.9 -021 8 3 .063 .109 .772 .869 .699 429.9 -022 6 3 .063 .141 .910 1.100 .444 639.5 -023 4 3 .063 .156 1.050 1.190 .279 888.4 -024 2 3 .063
14、.172 1.210 1.310 .177 1252.9 -025 1 3 .078 .172 1.350 1.520 .141 1556.6 -026 1/0 3 .078 .172 1.480 1.630 .111 1837.1 -027 2/0 3 .078 .187 1.680 1.840 .0893 2295.1 -028 3/0 3 .078 .203 1.820 2.030 .0708 2832.2 -029 4/0 3 .078 .203 1.990 2.180 .0562 3369.2 -030 250 3 .094 .203 2.140 2.360 .0476 3995.8
15、 -031 18 4 .031 .0625 .358 .421 7.49 85.2 -032 16 4 .031 .0625 .385 .450 4.70 104.8 -033 14 4 .047 .078 .523 .601 2.96 185.6 -034 12 4 .047 .094 .603 .689 1.86 258.4 -035 10 4 .047 .109 .664 .749 1.20 349.2 1/ THE MINIMUM INSULATION THICKNESS SHALL BE AT LEAST 90% OF THE NOMINAL. 2/ THE MINIMUM JACK
16、ET THICKNESS SHALL BE AT LEAST 90% OF THE NOMINAL. 3/ THE NOMINAL WEIGHT IS FOR INFORMATION ONLY. AEROSPACE STANDARD AS5756/3 SHEET 3 OF 4 REV. A CABLE, POWER, ELECTRICAL, 600 VOLTS, PORTABLE, MULTICONDUCTOR TABLE 1 DETAILS OF CONSTRUCTION (CONTD) PART NO. M5756/3 CONDUCTOR SIZE NUMBER OF CONDUCTORS
17、 NOMINAL INSULATIONTHICKNESS(INCH) 1/ NOMINAL JACKET THICKNESS(INCH) 2/ OVERALL DIAMETER OF JACKETED CABLECONDUCTOR RESISTANCE PER 1000 FEET (MAX) 20C (OHMS) NOMINAL WEIGHT PER1000 FEET (POUNDS) 3/ MIN (INCHES) MAX (INCHES) -036 8 4 .063 .109 .872 .975 .699 511.3 -037 6 4 .063 .125 1.020 1.140 .444
18、749.6 -038 4 4 .063 .156 1.170 1.300 .279 1095.5 -039 2 4 .063 .172 1.330 1.490 .177 1555.4 -040 1 4 .078 .172 1.510 1.660 .141 1941.6 -041 1/0 4 .078 .187 1.620 1.810 .111 2352.8 -042 2/0 4 .078 .203 1.840 2.050 .0893 2936.5 -043 3/0 4 .078 .203 2.020 2.220 .0708 3554.9 -044 4/0 4 .078 .203 2.180 2
19、.390 .0562 4246.3 -045 250 4 .094 .203 2.350 2.590 .0476 5052.8 -046 18 5 .031 .0625 .387 .452 7.49 99.5 -047 16 5 .031 .078 .417 .515 4.70 137.5 -048 14 5 .047 .094 .568 .682 2.96 238.5 -049 12 5 .047 .109 .655 .744 1.86 326.3 -050 10 5 .047 .109 .748 .842 1.20 413.6 -051 8 5 .063 .141 .948 1.090 .
20、699 693.4 -052 6 5 .063 .156 1.140 1.260 .444 968.6 -053 4 5 .063 .156 1.280 1.410 .279 1311.4 -054 2 5 .063 .172 1.480 1.620 .177 1869.4 -055 1 5 .078 .187 1.680 1.840 .141 2392.9 -056 1/0 5 .078 .203 1.800 2.010 .111 2899.6 -057 2/0 5 .078 .203 2.050 2.240 .0893 3544.5 -058 3/0 5 .078 .203 2.220 2
21、.430 .0708 4303.7 -059 4/0 5 .078 .203 2.400 2.620 .0562 5153.9 -060 250 5 .094 .203 2.590 2.840 .0476 6122.6 -061 18 6 .031 .078 .417 .516 7.49 128.0 -062 16 6 .031 .078 .479 .556 4.70 157.0 -063 14 6 .047 .094 .646 .734 2.96 273.2 -064 12 6 .047 .109 .709 .833 1.86 374.3 -065 10 6 .047 .125 .810 .
22、940 1.20 505.0 -066 8 6 .063 .156 1.060 1.210 .699 833.2 -067 6 6 .063 .156 1.230 1.370 .444 1120.4 -068 4 6 .063 .172 1.420 1.560 .279 1571.8 -069 2 6 .063 .187 1.610 1.790 .177 2231.6 -070 1 6 .078 .203 1.830 2.030 .141 2855.0 1/ THE MINIMUM INSULATION THICKNESS SHALL BE AT LEAST 90% OF THE NOMINA
23、L. 2/ THE MINIMUM JACKET THICKNESS SHALL BE AT LEAST 90% OF THE NOMINAL. 3/ THE NOMINAL WEIGHT IS FOR INFORMATION ONLY. AEROSPACE STANDARD AS5756/3 SHEET 4 OF 4 REV. A CABLE, POWER, ELECTRICAL, 600 VOLTS, PORTABLE, MULTICONDUCTOR TABLE 1 DETAILS OF CONSTRUCTION (CONTD) MILITARY PART NO. M5756/3 COND
24、UCTOR SIZE NUMBER OF CONDUCTORS NOMINAL INSULATIONTHICKNESS(INCH) 1/ NOMINAL JACKET THICKNESS(INCH) 2/ OVERALL DIAMETER OF JACKETED CABLECONDUCTOR RESISTANCE PER 1000 FEET (MAX) 20C (OHMS) NOMINAL WEIGHT PER1000 FEET (POUNDS) 3/ MIN (INCHES) MAX (INCHES) -071 1/0 6 .078 .203 1.990 2.180 .111 3388.0
25、-072 2/0 6 .078 .203 2.330 2.440 .0893 4147.1 -073 3/0 6 .078 .203 2.430 2.650 .0708 5046.1 -074 4/0 6 .078 .203 2.620 2.860 .0562 6053.0 -075 250 6 .094 .203 2.840 3.100 .0476 7227.5 -076 18 7 .031 .078 .417 .516 7.49 138.9 -077 16 7 .031 .078 .479 .556 4.70 172.0 -078 14 7 .047 .094 .646 .734 2.96
26、 300.3 -079 12 7 .047 .109 .709 .833 1.86 412.4 -080 10 7 .047 .125 .810 .940 1.20 557.8 -081 8 7 .063 .156 1.060 1.210 .699 921.6 -082 6 7 .063 .156 1.230 1.370 .444 1249.0 -083 4 7 .063 .172 1.420 1.560 .279 1760.2 -084 2 7 .063 .187 1.610 1.790 .177 2511.0 -085 1 7 .078 .203 1.830 2.030 .141 3216
27、.5 -086 1/0 7 .078 .203 1.990 2.180 .111 3829.7 -087 2/0 7 .078 .203 2.230 2.440 .0893 4699.9 -088 3/0 7 .078 .203 2.430 2.650 .0708 5736.5 -089 4/0 7 .078 .203 2.620 2.860 .0562 6898.8 -090 250 7 .094 .203 2.840 3.100 .0476 6122.6 1/ THE MINIMUM INSULATION THICKNESS SHALL BE AT LEAST 90% OF THE NOM
28、INAL. 2/ THE MINIMUM JACKET THICKNESS SHALL BE AT LEAST 90% OF THE NOMINAL. 3/ THE NOMINAL WEIGHT IS FOR INFORMATION ONLY. APPLICATION NOTES: 1. THE CABLE SPECIFIED UNDER THIS SPECIFICATION SHEET MAY BE INSULATED WITH ANY NUMBER OF INSULATING MATERIALS THAT WILL MEET THE LIMITED PERFORMANCE REQUIREM
29、ENTS OF THIS PARTICULAR SPECIFICATION SHEET. THERE ARE NO PERFORMANCE REQUIREMENTS FOR WEATHERING OR OZONE RESISTANCE ON CABLE COVERED BY THIS SPECIFICATION SHEET. THIS CABLE IS NOT RECOMMENDED FOR USE WHERE IT WILL BE EXPOSED TO THESE CONDITIONS. 2. CABLES COVERED UNDER THIS SPECIFICATION SHEET ARE
30、 GENERAL PURPOSE MULTICONDUCTOR CABLES THAT WERE PREVIOUSLY SPECIFIED IN AS5756B. THE CABLES SPECIFIED IN THIS SPECIFICATION SHEET ARE NOT AUTHORIZED FOR USE IN AS7974 CABLE ASSEMBLIES. A CHANGE BAR (|) LOCATED IN THE LEFT MARGIN IS FOR THE CONVENIENCE OF THE USER IN LOCATING AREAS WHERE TECHNICAL R
31、EVISIONS, NOT EDITORIAL CHANGES HAVE BEEN MADE TO THE PREVIOUS ISSUE OF THIS DOCUMENT. AN (R) SYMBOL TO THE LEFT OF THE DOCUMENT TITLE INDICATES A COMPLETE REVISION OF THE DOCUMENT, INCLUDING TECHNICAL REVISIONS. CHANGE BARS AND (R) ARE NOT USED IN ORIGINAL PUBLICATIONS NOR IN DOCUMENTS THAT CONTAIN EDITORIAL CHANGES ONLY.