1、BS EN ISO 1452-5:2009ICS 23.040.20; 23.040.45; 91.140.60; 93.025NO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAWBRITISH STANDARDPlastics piping systems for water supply and for buried and above-ground drainage and sewerage under pressure Unplasticized poly(vinyl chloride) (PVC-
2、U)Part 5: Fitness for purpose of the system (ISO 1452-5:2009)This British Standard was published under the authority of the Standards Policy and Strategy Committee on 31 January 2010 BSI 2010ISBN 978 0 580 59546 2Amendments/corrigenda issued since publicationDate CommentsBS EN ISO 1452-5:2009Nationa
3、l forewordThis British Standard is the UK implementation of EN ISO 1452-5:2009. Together with BS EN ISO 1452-1:2009, BS EN ISO 1452-2:2009, BS ENISO 1452-3:2009 and BS EN ISO 1452-4:2009, it supersedes BS EN1452-5:1999 and BS EN 1456-1:2001 which are withdrawn.The UK participation in its preparation
4、 was entrusted to Technical Committee PRI/88/2, Plastics piping for pressure applications.A list of organizations represented on this committee can be obtained on request to its secretary.This publication does not purport to include all the necessary provisions of a contract. Users are responsible f
5、or its correct application.Compliance with a British Standard cannot confer immunity from legal obligations.EUROPEAN STANDARD NORME EUROPENNE EUROPISCHE NORM EN ISO 1452-5 December 2009 ICS 93.025; 91.140.60; 23.040.20; 23.040.45 Supersedes EN 1452-5:1999, EN 1456-1:2001English Version Plastics pipi
6、ng systems for water supply and for buried and above-ground drainage and sewerage under pressure - Unplasticized poly(vinyl chloride) (PVC-U) - Part 5: Fitness for purpose of the system (ISO 1452-5:2009) Systmes de canalisations en plastique pour lalimentation en eau, pour branchements et collecteur
7、s dassainissement enterrs et ariens avec pression - Poly(chlorure de vinyle) non plastifi (PVC-U) - Partie 5: Aptitude lemploi du systme (ISO 1452-5:2009) Kunststoff-Rohrleitungssysteme fr die Wasserversorgung und fr erdverlegte und nicht erdverlegte Entwsserungs- und Abwasserdruckleitungen - Weichm
8、acherfreies Polyvinylchlorid (PVC-U) - Teil 5: Gebrauchstauglichkeit des Systems (ISO 1452-5:2009) This European Standard was approved by CEN on 4 November 2009. CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard
9、 the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN Management Centre or to any CEN member. This European Standard exists in three official versions (English, French, G
10、erman). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the same status as the official versions. CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Cyprus, Czec
11、h Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom. EUROPEAN COMMITTEE FOR STANDARDIZATION COMIT EURO
12、PEN DE NORMALISATION EUROPISCHES KOMITEE FR NORMUNG Management Centre: Avenue Marnix 17, B-1000 Brussels 2009 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. EN ISO 1452-5:2009: EBS EN ISO 1452-5:2009EN ISO 1452-5:2009 (E) 3 Foreword
13、This document (EN ISO 1452-5:2009) has been prepared by Technical Committee CEN/TC 155 “Plastics piping systems and ducting systems“, the secretariat of which is held by NEN, in collaboration with Technical Committee ISO/TC 138 “Plastics pipes, fittings and valves for the transport of fluids“. This
14、European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by June 2010, and conflicting national standards shall be withdrawn at the latest by June 2010. Attention is drawn to the possibility that some of the eleme
15、nts of this document may be the subject of patent rights. CEN and/or CENELEC shall not be held responsible for identifying any or all such patent rights. This document supersedes EN 1452-5:1999, EN 1456-1:2001. According to the CEN/CENELEC Internal Regulations, the national standards organizations o
16、f the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slo
17、vakia, Slovenia, Spain, Sweden, Switzerland and the United Kingdom. BS EN ISO 1452-5:2009ISO 1452-5:2009(E) ISO 2009 All rights reserved iiiContents Page Foreword iv Introduction.v 1 Scope1 2 Normative references1 3 Terms and definitions, symbols and abbreviations 2 4 Fitness for purpose of joints a
18、nd the system.2 4.1 Assemblies with non-end-load-bearing joints2 4.2 Assemblies with end-load-bearing joints .3 4.3 Short-term pressure test for leaktightness of assemblies3 4.4 Short-term negative pressure test for leaktightness of assemblies4 4.5 Long-term pressure test for leaktightness of assemb
19、lies 5 Annex A (normative) Assemblies of imperial (inch)-sized pipes, fittings, valves and ancillaries .7 Annex B (informative) Determination of the long-term test pressure by creep consideration.9 Bibliography13 BS EN ISO 1452-5:2009ISO 1452-5:2009(E) iv ISO 2009 All rights reservedForeword ISO (th
20、e International Organization for Standardization) is a worldwide federation of national standards bodies (ISO member bodies). The work of preparing International Standards is normally carried out through ISO technical committees. Each member body interested in a subject for which a technical committ
21、ee has been established has the right to be represented on that committee. International organizations, governmental and non-governmental, in liaison with ISO, also take part in the work. ISO collaborates closely with the International Electrotechnical Commission (IEC) on all matters of electrotechn
22、ical standardization. International Standards are drafted in accordance with the rules given in the ISO/IEC Directives, Part 2. The main task of technical committees is to prepare International Standards. Draft International Standards adopted by the technical committees are circulated to the member
23、bodies for voting. Publication as an International Standard requires approval by at least 75 % of the member bodies casting a vote. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. ISO shall not be held responsible for identifying
24、any or all such patent rights. ISO 1452-5 was prepared by the European Committee for Standardization (CEN) Technical Committee CEN/TC 155, Plastics piping systems and ducting systems, in collaboration with ISO Technical Committee ISO/TC 138, Plastics pipes, fittings and valves for the transport of f
25、luids, Subcommittee SC 2, Plastics pipes and fittings for water supplies, in accordance with the Agreement on technical cooperation between ISO and CEN (Vienna Agreement). This first edition cancels and replaces ISO 4422-5:1997, which has been technically revised. ISO 1452 consists of the following
26、parts, under the general title Plastics piping systems for water supply and for buried and above-ground drainage and sewerage under pressure Unplasticized poly(vinyl chloride) (PVC-U): Part 1: General Part 2: Pipes Part 3: Fittings Part 4: Valves Part 5: Fitness for purpose of the system Guidance fo
27、r the assessment of conformity is to form the subject of a part 7. BS EN ISO 1452-5:2009ISO 1452-5:2009(E) ISO 2009 All rights reserved vIntroduction The System Standard, of which this is Part 5, specifies the requirements for a piping system and its components made from unplasticized poly(vinyl chl
28、oride) (PVC-U). The piping system is intended to be used for water supply and for buried and above-ground drainage and sewerage under pressure. In respect of potential adverse effects on the quality of water intended for human consumption, caused by the products covered by this part of ISO 1452, the
29、 following are relevant. a) This part of ISO 1452 provides no information as to whether the products may be used without restriction; b) Existing national regulations concerning the use and/or the characteristics of these products remain in force. Requirements and test methods for components require
30、ments and test methods are specified in ISO 1452-2, ISO 1452-3 and ISO 1452-4. This part of ISO 1452 establishes the characteristics of fitness for purpose of the plastics piping system composed of pipes, fittings, valves, ancillaries and their joints. Guidance for installation is given in ISO/TR 41
31、911. Guidance for assessment of conformity is provided in ENV 1452-72. BS EN ISO 1452-5:2009BS EN ISO 1452-5:2009INTERNATIONAL STANDARD ISO 1452-5:2009(E) ISO 2009 All rights reserved 1Plastics piping systems for water supply and for buried and above-ground drainage and sewerage under pressure Unpla
32、sticized poly(vinyl chloride) (PVC-U) Part 5: Fitness for purpose of the system 1 Scope This part of ISO 1452 specifies the characteristics for the fitness for purpose of unplasticized poly(vinyl chloride) (PVC-U) piping systems intended for water supply and for buried and above-ground drainage and
33、sewerage under pressure. It also specifies the test parameters for the test methods referred to in this part of ISO 1452. In conjunction with ISO 1452-1, ISO 1452-2, ISO 1452-3 and ISO 1452-4, it is applicable to joints and assemblies with components of PVC-U, other plastics and non-plastics materia
34、ls intended to be used for the following: a) water mains and services buried in ground; b) conveyance of water above ground for both outside and inside buildings; c) buried and above-ground drainage and sewerage under pressure; It is applicable to piping systems intended for the supply of water unde
35、r pressure up to and including 25 C (cold water) intended for human consumption and for general purposes as well as for waste water under pressure. This part of ISO 1452 is also applicable to components for the conveyance of water and waste water up to and including 45 C. For temperatures between 25
36、 C and 45 C, Figure A.1 of ISO 1452-2:2009 applies. NOTE The producer and the end-user can come to agreement on the possibilities of use for temperatures above 45 C on a case-by-case basis. 2 Normative references The following referenced documents are indispensable for the application of this docume
37、nt. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. ISO 1452-1, Plastics piping systems for water supply and for buried and above-ground drainage and sewerage under pressure Unplasticized
38、poly(vinyl chloride) (PVC-U) Part 1: General ISO 1452-2:2009, Plastics piping systems for water supply and for buried and above-ground drainage and sewerage under pressure Unplasticized poly(vinyl chloride) (PVC-U) Part 2: Pipes BS EN ISO 1452-5:2009ISO 1452-5:2009(E) 2 ISO 2009 All rights reservedI
39、SO 1452-3:2009, Plastics piping systems for water supply and for buried and above-ground drainage and sewerage under pressure Unplasticized poly(vinyl chloride) (PVC U) Part 3: Fittings ISO 1452-4, Plastics piping systems for water supply and for buried and above-ground drainage and sewerage under p
40、ressure Unplasticized poly(vinyl chloride) (PVC U) Part 4: Valves ISO 13783, Plastics piping systems Unplasticized poly(vinyl chloride) (PVC-U) end-load-bearing double-socket joints Test method for leaktightness and strength while subjected to bending and internal pressure ISO 13844, Plastics piping
41、 systems Elastomeric-sealing-ring-type socket joints of unplasticized poly(vinyl chloride) (PVC-U) for use with PVC-U pipes Test method for leaktightness under negative pressure ISO 13845, Plastics piping systems Elastomeric-sealing-ring-type socket joints for use with unplasticized poly(vinyl chlor
42、ide) (PVC-U) pipes Test method for leaktightness under internal pressure and with angular deflection ISO 13846, Plastics piping systems End-load-bearing and non-end-load-bearing assemblies and joints for thermoplastics pressure piping Test method for long-term leaktightness under internal water pres
43、sure 3 Terms and definitions, symbols and abbreviations For the purposes of this document, the terms, definitions, symbols and abbreviated terms given in ISO 1452-1 apply. 4 Fitness for purpose of joints and the system 4.1 Assemblies with non-end-load-bearing joints The following types of assemblies
44、 with non-end-load-bearing joints shall fulfil the fitness for purpose requirements given in 4.3 to 4.5 and Tables 1 and 2, as applicable: a) integrally socketed PVC-U pipe to pipe assemblies with elastomeric ring seal joints conforming to ISO 1452-2; b) PVC-U fitting and pipe assemblies with elasto
45、meric ring seal joints conforming to ISO 1452-3 and ISO 1452-2, respectively; c) PVC-U valve and pipe assemblies with elastomeric ring seal joints conforming to ISO 1452-4 and ISO 1452-2, respectively; d) metal fitting and PVC-U pipe assemblies with elastomeric ring seal joints; e) metal valve and P
46、VC-U pipe assemblies with elastomeric ring seal joints; f) PVC-U, GRP or metal adaptor assemblies with elastomeric ring seal joints for PVC-U pipes and with flanged, threaded or other connections to pipes of different materials or to ancillary equipment, such as tapping saddles; g) mechanical joint
47、assemblies with PVC-U pipes. The components of the assemblies of types b) to g) shall be assembled with PVC-U pipes of the corresponding nominal pressure, PN, or pipe series S conforming to ISO 1452-2. The assembly instructions of the component manufacturer shall be followed. BS EN ISO 1452-5:2009IS
48、O 1452-5:2009(E) ISO 2009 All rights reserved 34.2 Assemblies with end-load-bearing joints The following types of assemblies with end-load-bearing joints shall fulfil the fitness for purpose requirements given in 4.3 to 4.5 and Table 1 and Table 2, as applicable: a) integral socketed PVC-U pipe to p
49、ipe assemblies with solvent cement joints conforming to ISO 1452-2; b) PVC-U fitting and pipe assemblies with solvent cement joints conforming to ISO 1452-3 and ISO 1452-2, respectively; c) flange assemblies with PVC-U pipes, using PVC-U flange adaptors and flanges conforming to ISO 1452-3 or using GRP or metal flanges; d) PVC-U valve and pipe assemblies with solvent cement joints conforming to ISO 1452-4 and ISO 1452-2, respectively; e) PVC-U or metal valve and PVC-U pipe assemblies with f