1、Designation: C 553 02Specification forMineral Fiber Blanket Thermal Insulation for Commercialand Industrial Applications1This standard is issued under the fixed designation C 553; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the
2、 year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the Department of Defense.1. Scope1.1 This specification covers t
3、he classification, composition,physical properties, and dimensions of mineral fiber (rock,slag, or glass) blanket intended for use as thermal insulation onsurfaces at temperatures below ambient or above ambient up to1200F (649C). For specific applications, the actual tempera-ture limit shall be agre
4、ed upon between the supplier and thepurchaser.1.2 The orientation of the fibers within the blanket isprimarily parallel to the principal surface (face). This specifi-cation does not cover fabricated pipe and tank wrap insulationwhere the insulation has been cut and fabricated to provide afiber orien
5、tation that is perpendicular to the surface (face).1.3 For satisfactory performance, properly installed protec-tive vapor retarders must be used in low temperature (belowambient) applications to prevent movement of water vaporthrough or around the insulation towards the colder surface.1.4 This stand
6、ard does not purport to provide the perfor-mance requirements of hourly-rated fire systems. Consult themanufacturer for the appropriate system.1.5 The values stated in inch-pound units shall be regardedas the standard. The System International (SI) equivalents ofinch-pound units are given in parenth
7、eses and are for informa-tion only and are approximate.1.6 This standard does not purport to address all of thesafety concerns associated with its use. It is the responsibilityof the user of this standard to establish appropriate safety andhealth practices and determine the applicability of regulato
8、rylimitations prior to use.2. Referenced Documents2.1 ASTM Standards:C 167 Test Methods for Thickness and Density of Blanketor Batt Thermal Insulations2C 168 Terminology Relating to Thermal Insulation2C 177 Test Method for Steady-State Heat Flux Measure-ments and Thermal Transmission Properties by M
9、eans ofthe Guarded-Hot-Plate Apparatus2C 390 Practice for Sampling and Acceptance of PreformedThermal Insulation Lots2C 411 Test Method for Hot-Surface Performance of High-Temperature Thermal Insulations2C 447 Practice for Estimating the Maximum Use Tempera-ture of Thermal Insulations2C 518 Test Met
10、hod for Steady-State Thermal TransmissionProperties by Means of the Heat Flow Meter Apparatus2C 665 Specification for Mineral-Fiber Blanket Thermal In-sulation for Light Frame Construction and ManufacturedHousing2C 680 Practice for Determination of Heat Gain or Loss andthe Surface Temperatures of In
11、sulated Pipe and EquipmentSystems by the Use of a Computer Program2C 1045 Practice for Calculating Thermal TransmissionProperties from Steady-State Heat Flux Measurements2C 1058 Practice for Selecting Temperatures for Evaluatingand Reporting Thermal Properties of Thermal Insulation2C 1101/C 1101M Te
12、st Method for Classifying the Flexibil-ity or Rigidity of Mineral Fiber Blanket and BoardInsulation2C 1104/C 1104M Test Method for Determining the WaterVapor Sorption of Unfaced Mineral Fiber Insulation2C 1114 Test Method for Steady-State Thermal TransmissionProperties by Means of the Thin-Heater Ap
13、paratus2C 1136 Specification for Flexible Low Permeance VaporRetarders for Thermal Insulations2C 1304 Test Method for Assessing the Odor Emission ofThermal Insulation Materials2C 1335 Test Method for Measuring the Non-Fibrous Con-tent of Man-Made Rock and Slag Mineral Fiber Insula-tions2E 84 Test Me
14、thod for Surface Burning Characteristics ofBuilding Materials32.2 Other Referenced Documents:CAN/ULC-S102M88 Standard Method of Test for Surface1This specification is under the jurisdiction of ASTM Committee C16 onThermal Insulation and is the direct responsibility of Subcommittee C16.23 onBlanket a
15、nd Loose Fill.Current edition approved Oct. 10, 2002. Published January 2003. Originallyapproved in 1964. Last previous edition approved 2001 as C 553 01.2Annual Book of ASTM Standards, Vol 04.06.3Annual Book of ASTM Standards, Vol 04.07.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C
16、700, West Conshohocken, PA 19428-2959, United States.Burning Characteristics of Building Materials and Assem-blies43. Terminology3.1 DefinitionsFor definitions used in this specification,refer to Terminology C 168.3.2 Definitions of Terms Specific to This Standard:3.2.1 mean temperaturethe sum of th
17、e cold surface tem-perature and the hot surface temperature divided by two.3.2.2 shotshot is defined, for the purposes of this docu-ment, as that material which cannot be brushed or mechani-cally shaken through No. 100 (150m) sieve.4. Classification4.1 Mineral fiber blanket insulation covered by thi
18、s speci-fication shall be classified into seven types shown in Table 1.The classification is based upon the insulations maximum usetemperature and apparent thermal conductivity.5. Ordering Information5.1 The type, dimensions, maximum use temperature, andfacing shall be specified by the purchaser. A
19、product certifica-tion (if required) shall be specified in the purchase order.6. Materials and Manufacture6.1 CompositionMineral fiber blanket insulation shall becomposed of rock, slag, or glass processed from the moltenstate into fibrous form bonded with an organic or inorganicbinder, or both. Asbe
20、stos shall not be used as an ingredient orcomponent part of the product.6.2 Facings:6.2.1 The purchaser shall specify whether the insulationshall be supplied plain or with facing, and if faced, shallspecify the type and its requirements.(WarningThe user of this specification is advised that themaxim
21、um use temperature of facing and adhesives may belower than the maximum use temperature of the insulation. Theuser of this specification shall ensure that sufficient insulationthickness is installed so that none of these accessory items(facings and adhesives) are exposed to temperatures abovetheir m
22、aximum use temperature. Practice C 680 can be used todetermine surface temperatures.)6.2.2 The vapor retarder facings shall be in accordance withspecification C 1136.6.2.3 Typical facing is as follows (others are available):6.2.3.1 Aluminum foil, reinforced fiber glass scrim, andnatural (brown) kraf
23、t paper laminate (facing) is known as FRKor FSK,6.2.3.2 White kraft paper, reinforced fiber glass scrim, andaluminum foil laminate (facing) is known as ASJ (All ServiceJacket),6.2.3.3 Aluminum foil, reinforced fiber glass scrim, andplastic film (example: polyethylene) laminate (facing) isknown as FS
24、P (Foil - Scrim - Polyethylene),6.2.3.4 Aluminum foil, and6.2.3.5 Vinyl film.7. Physical Property Requirements7.1 The insulation shall be classified as flexible, when testedin accordance with 11.7.7.2 The insulation type shall conform to the followingrequirements in Table 1: maximum use temperature,
25、 apparentthermal conductivity, water vapor sorption, and surface burn-ing characteristics.7.3 Odor EmissionA detectable odor of objectionablenature recorded by more than two of the five panel members4Available from Underwriters Laboratories of Canada, 7 Crouse Road, Scarbor-ough, Ontario, Canada M1R
26、 3A9.TABLE 1 Physical Property RequirementsAProperties Type I Type II Type III Type IV Type V Type VI Type VIIMaximum Use Temperature F (C)See Paragraph 6.2.1 - WarningUp to 450(232)Up to 450(232)Up to 450(232)Up to 850(454)Up to 1000(538)Up to 1000(538)Up to 1200(649)Apparent Thermal ConductivityMa
27、x. Btuin./hft2F (W/mK)Mean TemperaturesF (C)75 (24) 0.36 (0.052) 0.31 (0.045) 0.26 (0.038) 0.25 (0.036) 0.31 (0.045) 0.26 (0.038) 0.25 (0.036)100 (38) 0.39 (0.056) 0.33 (0.048) 0.28 (0.040) 0.27 (0.039) 0.33 (0.048) 0.28 (0.040) 0.27 (0.039)200 (93) 0.55 (0.079) 0.44 (0.063) 0.36 (0.052) 0.34 (0.049
28、) 0.44 (0.063) 0.36 (0.052) 0.34 (0.049)300 (149) 0.76 (0.110) 0.60 (0.087) 0.46 (0.066) 0.43 (0.062) 0.60 (0.087) 0.46 (0.066) 0.43 (0.062)400 (204) 0.55 (0.079) 0.89 (0.128) 0.60 (0.087) 0.55 (0.079)500 (260) 0.70 (0.101) 1.10 (0.159) 0.80 (0.115) 0.70 (0.101)600 (316) 1.50 (0.216) 1.05 (0.151) 0.
29、89 (0.128)700 (371) 1.13 (0.163)Water Vapor SorptionB% by Weight, max5.0 5.0 5.0 5.0 5.0 5.0 5.0Surface Burning CharacteristicsFlame Spread Index, max 25 25 25 25 25 25 25Smoke Developed Index, max 50 50 50 50 50 50 50AAdditional physical property requirements, refer to Section 7.BWater sorption cha
30、racteristics may change after the product is subject to elevated temperatures within normal service conditions.C553022shall constitute rejection of the material when tested inaccordance with 11.5.7.4 Corrosiveness to SteelWhen tested and evaluated inaccordance with 11.6, any corrosion resulting from
31、 the unfacedinsulation in contact with steel plates shall be judged to be nogreater than for comparative plates in contact with sterilecotton.(Warning There are facing adhesives that can causecorrosion to steel when in contact with water or water vaporand the steel. Currently, there is no test metho
32、d available tosatisfy every potential corrosion application.)7.5 Non-Fibrous (Shot) ContentThe averaged maximumshot content of rock or slag mineral fiber products, Types Ithrough VII as shown in Table 1, shall not exceed 30 % byweight as defined in 11.1. Non-fibrous content is not applicableto glass
33、 mineral fiber products.7.6 Maximum Use TemperatureShall be tested in accor-dance with 11.3, the insulation with facing shall not warp,flame or glow during hot surface exposure. No evidence ofmelting or fiber degradation shall be evident upon post-testinspection.7.7 Maximum Exothermic Temperature Ri
34、seShall betested in accordance with 11.3, the mid-point temperature shallnot at any point in time exceed the hot surface temperature bymore than 200F (111C). The 200F (111C) criterion appliesduring heat-up as well as steady state conditions. Exceedingthis limit shall constitute non-compliance to spe
35、cification andrejection.8. Dimensions and Permissible Variations8.1 The standard sizes and tolerances of mineral fiberblanket insulation are listed in Table 2. Specific sizes andtolerances shall be agreed upon between the purchaser andsupplier.8.2 The maximum density (determined in accordance withTe
36、st Method C 167) specified in Table 3 for Type(s) I throughType VII are for weight design purposes only.9. Workmanship9.1 The insulation shall have good workmanship and shallnot have defects which adversely affect its installation andperformance qualities.10. Sampling10.1 Inspection and qualificatio
37、n of the insulation shall be inaccordance with Criteria C 390, or as otherwise specified in thepurchase order or contract as agreed upon between the pur-chaser and the supplier.11. Test Methods11.1 Non-Fibrous (Shot) Content of Inorganic FibrousThermal InsulationShall be tested in accordance with Te
38、stMethod C 1335.11.2 Apparent Thermal Conductivity:11.2.1 The thermal conductivity as a function of tempera-ture for the representative specimens shall be determined withdata obtained from a series of thermal tests utilizing TestMethods C 177, C 518, or C 1114 as appropriate for thematerial under st
39、udy. Specimen shall be tested unfaced and ata maximum thickness of 2 in. (51 mm).11.2.1.1 Test Method C 518 shall not be used at tempera-tures or resistances other than those in the range of thecalibration.11.2.1.2 Test Method C 1114 shall not be used at tempera-tures or resistance ranges other than
40、 those with comparableresults to Test Method C 177.11.2.2 The test method selected shall have proven correla-tion with C 177 over the temperature range of conditions used.In cases of dispute, C 177 shall be considered as the finalauthority for material having flat geometry.11.2.3 Practice C 1058 sha
41、ll be used to obtain recommendedtest temperature combinations for testing purposes.11.2.4 As specified in C 1045, the range of test conditionsmust include at least one test where the hot surface temperatureis greater than, or equal to, the hot limit of the temperaturerange of desired data and at lea
42、st one test where the coldsurface temperature is less than, or equal to, the cold limit ofthe temperature range desired. Additional tests, at least twoadditional, shall be distributed somewhat evenly over the restof the temperature range.11.2.5 Final analysis of the thermal data shall be conductedin
43、 accordance with C 1045 to generate a thermal conductivityversus temperature relationship for the specimen.11.2.6 Final step of C 1045 analysis would be to calculatethe thermal conductivity using the equations generated at a setof mean temperatures for comparison to the specification.(Warning While
44、it is recommended that the specificationdata be presented as conductivity versus temperature, severalexisting specifications may contain mean temperature datafrom tests conducted at specific hot and cold surface tempera-tures. In these cases, the conductivity as a function of tempera-ture from the C
45、 1045 analysis may provide different results. Toinsure that the data is compatible, a C 680 analysis, using theconductivity versus temperature relationship from C 1045 andthe specific hot and cold surface temperatures, is required todetermine the effective thermal conductivity for comparison tothe s
46、pecification requirements.)TABLE 2 Sizes and TolerancesAMineral Fiber BlanketSizes TolerancesLengthRolls 50 ft. (15 m)75 ft. (23 m)100 ft. (30 m)150 ft. (48 m)200 ft. (61 m)0 in., excess permittedBlanket 24 in. (610 mm)36 in. (914 mm)48 in. (1219 mm)96 in. (2438 mm)612 in. (12.7 mm)WidthRolls 24 in.
47、 (610 mm)48 in. (1219 mm)96 in. (2438 mm)612 in. (12.7 mm)Blanket 12 in. (305 mm)24 in. (610 mm)36 in. (914 mm)48 in. (1219 mm)612 in. (12.7 mm)Thickness1 in. (25.4 mm) to 6 in. (152mm) in12in. (12.7 mm)increments18in. (3.2 mm) excesspermittedAOther sizes available upon request.C55302311.3 Maximum U
48、se Temperature and Exothermic Tempera-ture RiseShall be tested in accordance with Test MethodC 411 and the hot surface performance section of PracticeC 447 at the manufacturers maximum recommend thicknessfor each temperature. The test surface shall be at the intendedsurface temperature when test beg
49、ins. No special requirementsfor heat-up shall be specified by the manufacturer to qualifyproduct compliance with either maximum use temperature ormaximum exothermic temperature rise.11.4 Surface Burning CharacteristicsTest in accordancewith Test Method E 84. For Canada, test in accordance withTest Method CAN/ULC-S102M88. Test with facing andadhesive in place, if facing is intended to be on the end product.11.5 Odor EmissionTest in accordance with Test MethodC 1304.11.6 Corrosion to SteelTest in accordance with the cor-rosiveness method of Spe