ANSI ASHRAE 199 ERTA-2017 Method of Testing the Performance of Industrial Pulse Cleaned Dust Collectors.pdf
-
资源ID:431500
资源大小:67.83KB
- 资源格式: PDF
下载积分:2000积分
快捷下载

账号登录下载
微信登录下载
下载资源需要2000积分(如需开发票,请勿充值!)
友情提示
2、PDF文件下载后,可能会被浏览器默认打开,此种情况可以点击浏览器菜单,保存网页到桌面,就可以正常下载了。
3、本站不支持迅雷下载,请使用电脑自带的IE浏览器,或者360浏览器、谷歌浏览器下载即可。
4、本站资源下载后的文档和图纸-无水印,预览文档经过压缩,下载后原文更清晰。
5、试题试卷类文档,如果标题没有明确说明有答案则都视为没有答案,请知晓。
|
ANSI ASHRAE 199 ERTA-2017 Method of Testing the Performance of Industrial Pulse Cleaned Dust Collectors.pdf
1、2017 ASHRAE. All rights reserved. ERRATA SHEET FOR ANSI/ASHRAE STANDARD 199-2016 Method of Testing the Performance of Industrial Pulse Cleaned Dust Collectors February 2, 2017 The corrections listed in this errata sheet apply to ANSI/ASHRAE Standard 199-2016. The first printing is identified on the
2、outside back cover as “Product code: 86624 6/16”. Page Erratum 7 6.1 Test Dust. Figure 6-1 was inadvertently omitted from the publication of Standard 199. Immediately following Bulk Density insert Figure 6-1 as shown below. 6.1 Test Dust. Test dust shall be fine ground calcium carbonate (wet ground
3、marble) with the following typical properties: CaCO3: 95% Hegman gauge: 6 Moisture: 0.12% Plus 325 mesh: 0.003% Particle size: 0.3 to 10 m range, 3.0 m median Specific Gravity: 2.7 Bulk Density: 40lb/ft3(641 kg/m3) loose, 65lb/ft3(1041 kg/m3) packed Figure 6-1: Typical particle size distribution (determined by Micromeritics SediGraph) Test dust shall be stored in original unopened packaging in the conditions stated in Section 5.6.