1、BSI Standards PublicationWB11885_BSI_StandardCovs_2013_AW.indd 1 15/05/2013 15:06Fire resistance tests for non-loadbearing elementsPart 2: CeilingsBS EN 1364-2:2018EUROPEAN STANDARD NORME EUROPENNE EUROPISCHE NORM EN 1364-2 January 2018 ICS 13.220.50; 91.060.30 Supersedes EN 1364-2:1999English Versi
2、on Fire resistance for tests for non-loadbearing elements - Part 2: Ceilings Essais de rsistance au feu des lments non porteurs -Partie 2: Plafonds Feuerwiderstandsprfungen fr nichttragende Bauteile - Teil 2: Unterdecken This European Standard was approved by CEN on 8 October 2017. CEN members are b
3、ound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the
4、 CEN-CENELEC Management Centre or to any CEN member. This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management Centr
5、e has the same status as the official versions. CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania
6、, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and United Kingdom. EUROPEAN COMMITTEE FOR STANDARDIZATION COMIT EUROPEN DE NORMALISATION EUROPISCHES KOMITEE FR NORMUNG CEN-CENELEC Management Centre: Rue de la Scienc
7、e 23, B-1040 Brussels 2018 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. EN 1364-2:2018 ENational forewordThis British Standard is the UK implementation of EN 1364-2:2018. It supersedes BS EN 1364-2:1999, which is withdrawn.The UK p
8、articipation in its preparation was entrusted to Technical Committee FSH/22/-/7, Non loadbearing separating elements.A list of organizations represented on this committee can be obtained on request to its secretary.This publication does not purport to include all the necessary provisions of a contra
9、ct. Users are responsible for its correct application. The British Standards Institution 2018 Published by BSI Standards Limited 2018ISBN 978 0 580 83887 3ICS 13.220.50Compliance with a British Standard cannot confer immunity from legal obligations. This British Standard was published under the auth
10、ority of the Standards Policy and Strategy Committee on 28 February 2018.Amendments/corrigenda issued since publicationDate Text affectedBRITISH STANDARDBS EN 1364-2:2018EUROPEAN STANDARD NORME EUROPENNE EUROPISCHE NORM EN 1364-2 January 2018 ICS 13.220.50; 91.060.30 Supersedes EN 1364-2:1999English
11、 Version Fire resistance for tests for non-loadbearing elements - Part 2: Ceilings Essais de rsistance au feu des lments non porteurs -Partie 2: Plafonds Feuerwiderstandsprfungen fr nichttragende Bauteile - Teil 2: Unterdecken This European Standard was approved by CEN on 8 October 2017. CEN members
12、 are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application
13、to the CEN-CENELEC Management Centre or to any CEN member. This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management
14、 Centre has the same status as the official versions. CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lit
15、huania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and United Kingdom. EUROPEAN COMMITTEE FOR STANDARDIZATION COMIT EUROPEN DE NORMALISATION EUROPISCHES KOMITEE FR NORMUNG CEN-CENELEC Management Centre: Rue de la
16、Science 23, B-1040 Brussels 2018 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. EN 1364-2:2018 EBS EN 1364-2:2018EN 1364-2:2018 (E) 2 Contents Page European foreword . 4 Introduction 5 1 Scope 6 2 Normative references 6 3 Terms and d
17、efinitions . 6 4 Test equipment 7 5 Test conditions . 7 6 Test specimen . 7 6.1 Size 7 6.1.1 Self-supporting ceilings exposed to fire from below or from above 7 6.1.2 Suspended ceilings exposed to fire from below or from above 7 6.2 Number . 8 6.3 Design 8 6.3.1 General 8 6.3.2 Orientation 8 6.3.3 S
18、upport conditions . 8 6.4 Construction 9 6.5 Verification 9 7 Installation of test specimen . 9 7.1 General 9 7.2 Supporting construction . 9 7.2.1 General 9 7.2.2 Exposure to fire from below 9 7.2.3 Exposure to fire from above 9 8 Conditioning . 10 9 Application of instrumentation 10 9.1 Thermocoup
19、les . 10 9.1.1 Furnace thermocouples (plate thermometers) 10 9.1.2 Unexposed surface thermocouples . 10 9.2 Pressure . 11 10 Test procedure 11 10.1 Fire test 11 10.2 Pressure control . 11 10.3 Integrity . 11 10.4 Insulation 11 10.5 Observations during the test 11 11 Performance criteria 12 11.1 Gene
20、ral . 12 11.2 Integrity . 12 11.2.1 Fire from below . 12 11.2.2 Fire from above . 12 BS EN 1364-2:2018EN 1364-2:2018 (E) 3 11.3 Insulation . 12 12 Test report 12 13 Field of direct application of test results . 12 13.1 General . 12 13.2 Self-supporting ceilings exposed to fire from below or from abo
21、ve 12 13.2.1 Size . 12 13.2.2 Fittings 13 13.2.3 Cavities above self-supporting ceilings 13 13.2.4 Cables, pipes, etc. above the ceiling . 13 13.3 Suspended ceilings with fire from below . 13 13.3.1 Size . 13 13.3.2 Fittings 14 13.3.3 Cavity . 14 13.3.4 Length of supporting hangers 14 13.3.5 Cables,
22、 pipes, etc. above the ceiling . 14 13.4 Suspended ceilings with fire from above . 14 13.4.1 Size . 14 13.4.2 Cavity . 14 13.4.3 Length of supporting hangers 14 13.4.4 Supporting construction with fire from above 14 13.4.5 Cables, pipes, etc. above the ceiling . 14 13.5 Ceilings incorporating self-s
23、upporting and suspended parts with fire from below 15 13.5.1 Size . 15 13.5.2 Fittings 15 13.5.3 Cavity . 15 13.5.4 Length of supporting hangers 15 13.5.5 Cables, pipes etc. above the ceiling 15 13.6 Ceilings incorporating self-supporting and suspended parts with fire from above 15 13.6.1 Size . 15
24、13.6.2 Cavity . 15 13.6.3 Length of supporting hangers 15 13.6.4 Supporting construction with fire from above 15 13.6.5 Cables, pipes, etc. above the ceiling . 16 Bibliography . 24 BS EN 1364-2:2018EN 1364-2:2018 (E) 4 European foreword This document (EN 1364-2:2018) has been prepared by Technical C
25、ommittee CEN/TC 127 “Fire safety in buildings”, the secretariat of which is held by BSI. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by July 2018, and conflicting national standards shall be with
26、drawn at the latest by July 2018. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN shall not be held responsible for identifying any or all such patent rights. This document supersedes EN 1364-2:1999. This European Standard has
27、 been prepared under a mandate given to CEN by the European Commission and the European Free Trade Association. The main changes with respect to the previous edition are listed below: a) locations of thermocouples are modified in line with the definitions in EN 1363-1; b) a more precise definition o
28、f the test specimen; c) more precise rules in the field of direct application. EN 1364 Fire resistance tests for non-loadbearing elements consists of the following: Part 1: Walls Part 2: Ceilings Part 3: Curtain walling full configuration Part 4: Curtain walling part configuration Part 5: Air transf
29、er grilles According to the CEN-CENELEC Internal Regulations, the national standards organisations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia,
30、France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom. BS EN 1364-2:2018EN 1364-2:2018 (E) 5 Introduction This European Sta
31、ndard has been prepared to provide a method of test for assessing the fire resistance of non-loadbearing ceilings. It is applicable to self-supporting ceilings as well as suspended ceilings, with either fire from below of from above. This European Standard is not applicable to loadbearing systems. T
32、he fire resistance of loadbearing floors in conjunction with a suspended ceiling should be assessed by using EN 1365-2. Caution The attention of all persons concerned with managing and carrying out this fire resistance test is drawn to the fact that fire testing may be hazardous and that there is a
33、possibility that toxic and/or harmful smoke and gases may be evolved during the test. Mechanical and operational hazards may also arise during the construction of the test elements or structures, their testing and disposal of test residues. An assessment of all potential hazards and risks to health
34、should be made and safety precautions should be identified and provided. Written safety instructions should be issued. Appropriate training should be given to relevant personnel. Laboratory personnel should ensure that they follow written safety instructions at all times. Safety note Monitoring for
35、integrity by the cotton pad or other means and insulation by use of the roving thermocouple from above a test specimen (in the case of fire from below) or within a void beneath a fire test specimen (in the case of fire from above) can be hazardous unless the risks associated with these practices are
36、 considered and appropriate precautions taken to protect operators from radiation, smoke, hot gases and from contact with furnace flame. Operators should not reach over the test specimen (in the case of fire from below) or enter the void beneath a test specimen (in the case of fire from above) to ca
37、rry out inspection tests of any type during the test. BS EN 1364-2:2018EN 1364-2:2018 (E) 6 1 Scope This part of EN 1364 specifies a method for determining the fire resistance of ceilings, which in themselves possess fire resistance independent of any building element above them. This European Stand
38、ard is used in conjunction with EN 1363-1. The method is applicable to ceilings, which are either suspended by hangers or fixed directly to a supporting frame or construction, and to self-supporting ceilings. Within this test method, the ceiling is exposed to fire, with the exposure being applied ei
39、ther: a) from below the ceiling, or b) from above the ceiling to simulate fire within the cavity above the ceiling. The contribution to fire resistance which a suspended ceiling might provide as a protective membrane to loadbearing elements is determined using the procedure given in EN 13381-1. The
40、fire resistance of loadbearing floors in conjunction with a suspended ceiling can also be assessed by using tests according to EN 1365-2. 2 Normative references The following documents, in whole or in part, are normatively referenced in this document and are indispensable for its application. For da
41、ted references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 1363-1:2012, Fire resistance tests - Part 1: General Requirements EN 1363-2, Fire resistance tests - Part 2: Alternative and additional procedu
42、res EN ISO 13943, Fire safety - Vocabulary (ISO 13943) 3 Terms and definitions For the purposes of this document, the terms and definitions given in EN 1363-1 and EN ISO 13943 and the following apply. 3.1 ceiling non-loadbearing element of a building construction designed to provide horizontal fire
43、separation 3.2 self-supporting ceiling ceiling with a span between building constructions, without any additional hangers 3.3 suspended ceiling ceiling which is suspended from a supporting construction 3.4 cavity space between the upper surface of the ceiling and the underside of any floor, roof or
44、its supporting construction BS EN 1364-2:2018EN 1364-2:2018 (E) 7 3.5 test specimen full ceiling specimen submitted for test, including hangers, fittings, insulating materials and features such as lighting, ventilation and access and inspection panels 3.6 supporting construction loadbearing construc
45、tion to which a ceiling is attached for the test 3.7 fittings devices penetrating the ceiling EXAMPLE Lighting and ventilation systems not otherwise covered by a specific fire test. 3.8 overrun time period of fire resistance (expressed in minutes) beyond the intended classification period achieved i
46、n the test 4 Test equipment The test equipment shall be as specified in EN 1363-1:2012, Clause 4 or, if appropriate, EN 1363-2. 5 Test conditions The heating and pressure conditions and the furnace atmosphere shall conform to the requirements given in EN 1363-1:2012, Clause 5 or, if applicable, EN 1
47、363-2. 6 Test specimen 6.1 Size 6.1.1 Self-supporting ceilings exposed to fire from below or from above When the ceiling in practice is equal to or greater than the size of the furnace opening, then it shall be tested at a size of at least 4 m 3 m. The span of the ceiling shall be in the direction o
48、f the larger dimension (see also 6.3.2). When the ceiling in practice is smaller than 4 m 3 m, in either direction, then it shall be tested at full size. The furnace aperture shall be closed with some elements of adequate size, with the stiffness and stability required to support the test specimen.
49、6.1.2 Suspended ceilings exposed to fire from below or from above The test specimen shall be of size so that at least 4 m 3 m is exposed to the furnace conditions. The direction of the main components (see 6.3.2) shall be in the direction of the larger dimension. When the ceiling in practice is smaller than 4 m 3 m, in either direction, then it shall be tested at full size. The furnace aperture shall be closed with some elements of adequate size, with the stiffness and stability required to support the test specimen. BS EN 1364-2:2018EN