1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL UL 1635 Digital Alarm Communicator System Units STANDARD FOR SAFETYUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM ULUL COPYRIGHTED MATER
2、IAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL UL Standard for Safety for Digital Alarm Communicator System Units, UL 1635 Fourth Edition, Dated April 13, 2018 Summary of Topics The fourth edition of the Standard for Digital Alarm Communicator System Units, UL
3、 1635, was issued to revise the operation requirements. The revised requirements are substantially in accordance with Proposal(s) on this subject dated January 17, 2014 and October 21, 2016. All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmit
4、ted in any form by any means, electronic, mechanical photocopying, recording, or otherwise without prior permission of UL. UL provides this Standard as is without warranty of any kind, either expressed or implied, including but not limited to, the implied warranties of merchantability or tness for a
5、ny purpose. In no event will UL be liable for any special, incidental, consequential, indirect or similar damages, including loss of prots, lost savings, loss of data, or any other damages arising out of the use of or the inability to use this Standard, even if UL or an authorized UL representative
6、has been advised of the possibility of such damage. In no event shall ULs liability for any damage ever exceed the price paid for this Standard, regardless of the form of the claim. Users of the electronic versions of ULs Standards for Safety agree to defend, indemnify, and hold UL harmless from and
7、 against any loss, expense, liability, damage, claim, or judgment (including reasonable attorneys fees) resulting from any error or deviation introduced while purchaser is storing an electronic Standard on the purchasers computer system. APRIL 13, 2018 UL 1635 tr1UL COPYRIGHTED MATERIAL NOT AUTHORIZ
8、ED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL APRIL 13, 2018 UL 1635 tr2 No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL APRIL 13, 2018 1 UL 1635 Standard for Digital Alarm Communicator System Uni
9、ts First Edition January, 1985 Second Edition February, 1991 Third Edition January, 1996 Fourth Edition April 13, 2018 This ANSI/UL Standard for Safety consists of the Fourth Edition. The most recent designation of ANSI/UL 1635 as an American National Standard (ANSI) occurred on April 13, 2018. ANSI
10、 approval for a standard does not include the Cover Page, Transmittal Pages, and Title Page. Comments or proposals for revisions on any part of the Standard may be submitted to UL at any time. Proposals should be submitted via a Proposal Request in ULs On-Line Collaborative Standards Development Sys
11、tem (CSDS) at https:/. ULs Standards for Safety are copyrighted by UL. Neither a printed nor electronic copy of a Standard should be altered in any way. All of ULs Standards and all copyrights, ownerships, and rights regarding those Standards shall remain the sole and exclusive property of UL. COPYR
12、IGHT 2018 UNDERWRITERS LABORATORIES INC. ANSI/UL1635-2018UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL APRIL 13, 2018 DIGITAL ALARM COMMUNICATOR SYSTEM UNITS - UL 1635 2 No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHE
13、R REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL CONTENTS INTRODUCTION 1 Scope .7 2 Components8 3 Units of Measurement .9 4 Undated References 9 5 Terminology 9 6 Glossary .9 7 Installation and Operating Instructions 11 8 Electric Shock .12 CONSTRUCTION ASSEMBLY 9 General.13 9.1 Product ass
14、embly .13 9.2 Electrical protection 13 10 Protection of Service Personnel 18 11 Enclosures .18 11.1 General .18 11.2 Doors and covers 20 11.3 Enclosure openings 20 11.4 Screens and expanded metal 22 11.5 Cast metal.22 11.6 Sheet metal .23 11.7 Product enclosure mounting .26 11.8 Polymeric materials.
15、26 12 Corrosion Protection 26 FIELD WIRING CONNECTIONS 13 General27 14 Cord Connected Products .27 15 Permanently Connected Products.28 15.1 General .28 15.2 Field-wiring terminals .29 15.3 Field wiring leads.31 15.4 Polarity identication 32 16 Grounding .32 INTERNAL WIRING 17 General34 18 Wiring Me
16、thods.34 19 Separation of Circuits .35 20 Bonding for Grounding 36 APRIL 13, 2018 DIGITAL ALARM COMMUNICATOR SYSTEM UNITS - UL 1635 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL COMPONENTS, ELECTRICAL 21 General40 21.1 Mounting of compone
17、nts 40 21.2 Insulating materials .41 21.3 Fuseholder 42 21.4 Current-carrying parts.42 21.5 Power-on indicator .42 22 Overcurrent Protection 42 23 Semiconductors 42 24 Switches.42 25 Transformers and Coils43 SPACINGS 26 General43 27 Components .46 PERFORMANCE ALL UNITS 28 General46 28.1 Test units a
18、nd data .46 28.2 Test samples and miscellaneous data 47 28.3 Test voltages 47 28.4 FCC requirements 48 29 Operation 48 30 Subscribers Control Units .52 31 Circuit and Operation of Subscriber Control Unit52 32 Normal Operation Test 53 33 Incorrect Connection Tests.53 34 Input Test54 35 Output Measure
19、ment Test .54 36 Electrical Supervision Test .55 37 Undervoltage Operation Test .55 38 Overvoltage Operation Test 55 39 Variable Ambient Test .56 40 Humidity Test 56 41 Leakage Current Tests for Cord-Connected Products .56 42 Electric Shock Current Test 60 43 Overload Test 64 43.1 General .64 43.2 S
20、eparately energized circuits 64 44 Endurance Test 65 44.1 General .65 45 Jarring Test 65 46 Dielectric Voltage-Withstand Test .66 47 Temperature Test.67 48 Abnormal Operation Test 71 49 Electrical Transient Tests 71 49.1 General .71 49.2 Supply line transients .71 49.3 Internally induced transients
21、.73 49.4 Input/output circuit transients 73 APRIL 13, 2018 DIGITAL ALARM COMMUNICATOR SYSTEM UNITS - UL 1635 4UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL 50 AC Induction Test.74 51 Polymeric Materials Test.74 52 Battery Replacement Test
22、.75 53 Drop Test 75 54 Strain Relief Test .76 54.1 Supply cord .76 54.2 Field-wiring leads.76 55 Ignition Through Bottom-Panel Openings Tests.76 55.1 General .76 55.2 Hot, aming oil .76 55.3 Molten PVC and copper.77 56 Mechanical Strength Tests for Enclosures .78 57 Special Terminal Assemblies Tests
23、 .78 57.1 General .78 57.2 Disconnection and reconnection .79 57.3 Flexing test 79 57.4 Millivolt drop test .79 57.5 Temperature test .80 58 Attack Tests80 INTRUSION DETECTION 59 General81 POWER SUPPLIES GENERAL CONSTRUCTION 60 General81 RECHARGEABLE (SECONDARY) BATTERIES 61 General82 PERFORMANCE 62
24、 Power Failure 83 63 Operation 84 64 Digital Alarm Communicator Receiver Power Supply 85 SHORT RANGE RADIO FREQUENCY (RF) DEVICES 65 General85 66 Time to Report Alarm .86 67 Inoperative Transmitter Reporting.86 68 Battery Status Indication .87 69 Tamper Protection 87 70 Interference Protection 88 71
25、 Reference Level Determination .88 71.1 Method I 88 71.2 Method 2 90 72 Interference Immunity .93 73 Frequency Selectivity94 APRIL 13, 2018 DIGITAL ALARM COMMUNICATOR SYSTEM UNITS - UL 1635 5UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL 74
26、 Clash95 75 Clash Error 96 76 Error (Falsing) Rate .96 77 Throughput Rate98 78 Transmitter Stability Test 99 79 Transmitter Accelerated Aging Test .99 80 Installation Instructions and User Manual 99 MANUFACTURING AND PRODUCTION-LINE TESTS FOR HIGH-VOLTAGE PRODUCTS 81 General 100 82 Production-Line D
27、ielectric Voltage-Withstand Test .100 83 Production-Line Grounding Continuity Test .101 MARKING 84 General 101 85 Marking Permanency Tests .104 ACCESSORY EQUIPMENT 86 General 104 87 Construction 104 88 Performance (Installation Test) 105 89 Marking 105 APPENDIX A Standards for ComponentsA1 APRIL 13,
28、 2018 DIGITAL ALARM COMMUNICATOR SYSTEM UNITS - UL 1635 6UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL INTRODUCTION 1 Scope 1.1 These requirements cover digital alarm communicator system units for use in central-station burglar-alarm syste
29、ms, proprietary burglar alarm systems, police station connect burglar-alarm systems, residential burglar-alarm systems, residential re warning systems, and home health care medical alert systems. 1.2 As covered by these requirements, a digital alarm communicator system consists of a digital alarm co
30、mmunicator transmitter interconnected to or integral with: a) A central-station burglar-alarm control unit, b) A proprietary burglar alarm control unit, c) A police-station-connect burglar-alarm control unit, d) A residential burglar-alarm control unit, e) A residential re warning control unit, or f
31、) A home health care medical alert control unit. A need for off premises transmission will activate the digital alarm communicator transmitter that contacts a digital alarm communicator receiver located at a central-station or residential monitoring station through the telephone companys switched ne
32、twork (dial system) and transmits a message identifying the change in condition at the protected premises or residence. 1.3 The operation of a digital alarm communicator system is under the control of the owner or others interested in the property, the occupants of the residence, and the operators a
33、t the central-station or residential monitoring station. 1.4 If equipment covered by these requirements is intended for use in a combination burglar-alarm and re-protective signaling system, the portion of the equipment serving a re-alarm function shall comply with the Standard for Control Units and
34、 Accessories for Fire Alarm Systems, UL 864. 1.5 Service required to be provided by the central-station is covered by the Standard for Central-Station Alarm Services, UL 827. 1.6 A digital alarm communicator system may be classied as police-station connected if: a) It is used in combination with a p
35、rotected premises control unit, an alarm sounding device, and an alarm housing that complies with the Standard for Police Station Connected Burglar Alarm Units and Systems, UL 365, and b) The signals are transmitted to a digital burglar-alarm communicator receiver located at a central-station that c
36、omplies with the Standard for Central-Station Alarm Services, UL 827. APRIL 13, 2018 DIGITAL ALARM COMMUNICATOR SYSTEM UNITS - UL 1635 7UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL 1.7 Devices installed on individual properties are furthe
37、r classied as to extent of protection at each location, according to the requirements covering installation and classication (of extent) of alarm equipment at individual locations as published in the Standard for Installation and Classication of Burglar and Holdup Alarm Systems, UL 681, that should
38、be consulted by burglar-alarm installers. 1.8 Digital alarm communicator units for use in residential burglar-alarm systems shall comply with the Standard for Household Burglar-Alarm System Units, UL 1023, in addition to the applicable requirements in this standard. 1.9 Digital alarm communicator un
39、its for use in residential re warning systems shall comply with the Standard for Household Fire Warning System Units, UL 985, in addition to the applicable requirements in this standard. 1.10 Digital alarm communicator units for use in home health care medical alert systems shall comply with the Sta
40、ndard for Home Health Care Signaling Equipment, UL 1637, in addition to the applicable requirements in this standard. 2 Components 2.1 Except as indicated in 2.2 a component of a product covered by this standard shall comply with the requirements for that component. See Appendix A for a list of stan
41、dards covering components generally used in the products covered by this standard. 2.2 A component is not required to comply with a specic requirement that: a) Involves a feature or characteristic not required in the application of the component in the product covered by this standard, or b) Is supe
42、rseded by a requirement in this standard. 2.3 A component shall be used in accordance with its rating established for the intended conditions of use. 2.4 Specic components are incomplete in construction features or restricted in performance capabilities. Such components are intended for use only und
43、er limited conditions, such as certain temperatures not exceeding specied limits, and shall be used only under those specic conditions. APRIL 13, 2018 DIGITAL ALARM COMMUNICATOR SYSTEM UNITS - UL 1635 8UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION
44、 FROM UL 3 Units of Measurement 3.1 Values stated without parentheses are the requirement. Values in parentheses are explanatory or approximate information. 3.2 Unless otherwise indicated, all voltage and current values specied in this standard are rms. 4 Undated References 4.1 Any undated reference
45、 to a code or standard appearing in the requirements of this standard shall be interpreted as referring to the latest edition of that code or standard. 5 Terminology 5.1 The term product as used in this standard refers to all types of digital alarm communicator units. 6 Glossary 6.1 For the purpose
46、of this standard, the following denitions apply. 6.2 ACKNOWLEDGMENT SIGNAL An audible and/or visual signal that is sent to the subscriber by the central station to notify the subscriber that a signal has been received indicating that the protection system has been properly armed. The acknowledgment
47、signal is to be sent manually or automatically. 6.3 CIRCUITS, ELECTRICAL: a) High-Voltage A circuit involving a potential of not more than 600 volts and having circuit characteristics in excess of those of a low-voltage power-limited circuit. b) Low-Voltage A circuit involving a potential of not mor
48、e than 30 volts AC rms, 42.4 volts DC or AC peak. c) Power Limited A circuit whose output is limited as specied in Tables 6.1 and 6.2. The power limitation shall be provided by the construction of the transformer, a xed impedance, a noninterchangeable fuse, a nonadjustable manual reset circuit prote
49、ctive device, or a regulating network. APRIL 13, 2018 DIGITAL ALARM COMMUNICATOR SYSTEM UNITS - UL 1635 9UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL Table 6.1 Power limitations for inherently limited power source (overcurrent protection not required) Circuit voltage V max b AC-DC (volts) Maximum nameplate ratings Current limitation I max b (amperes) VA (volt amperes) Current (amperes) 0to20 5.0 V max a 5.0 8.0 over 20 to 30 100 100/V ma