1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL UL 1567 Receptacles and Switches Intended for Use with Aluminum WireUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM ULUL COPYRIGHTED MATE
2、RIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL UL Standard for Safety for Receptacles and Switches Intended for Use with Aluminum Wire, UL 1567 Fifth Edition, Dated March 16, 2012 Summary of Topics This new edition of UL 1567 is being issued to reect the desi
3、gnation of UL 1567 as an ANSI standard. All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form by any means, electronic, mechanical photocopying, recording, or otherwise without prior permission of UL. UL provides this Standard as
4、 is without warranty of any kind, either expressed or implied, including but not limited to, the implied warranties of merchantability or tness for any purpose. In no event will UL be liable for any special, incidental, consequential, indirect or similar damages, including loss of prots, lost saving
5、s, loss of data, or any other damages arising out of the use of or the inability to use this Standard, even if UL or an authorized UL representative has been advised of the possibility of such damage. In no event shall ULs liability for any damage ever exceed the price paid for this Standard, regard
6、less of the form of the claim. Users of the electronic versions of ULs Standards for Safety agree to defend, indemnify, and hold UL harmless from and against any loss, expense, liability, damage, claim, or judgment (including reasonable attorneys fees) resulting from any error or deviation introduce
7、d while purchaser is storing an electronic Standard on the purchasers computer system. The requirements in this Standard are now in effect, except for those paragraphs, sections, tables, gures, and/or other elements of the Standard having future effective dates as indicated in the note following the
8、 affected item. The prior text for requirements that have been revised and that have a future effective date are located after the Standard, and are preceded by a SUPERSEDED REQUIREMENTS notice. MARCH 16, 2012 UL 1567 tr1UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION
9、 WITHOUT PERMISSION FROM UL MARCH 16, 2012 UL 1567 tr2 No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL MARCH 16, 2012 1 UL 1567 Standard for Receptacles and Switches Intended for Use with Aluminum Wire First Edition May,
10、1984 Second Edition July, 1993 Third Edition November, 1998 Fourth Edition December, 2006 Fifth Edition March 16, 2012 The most recent designation of ANSI/UL 1567 as an American National Standard (ANSI) occurred on March 16, 2012. The ANSI approval for this standard does not include the Cover Page,
11、Transmittal Pages, Title Page, or effective date information. This ANSI/UL Standard for Safety consists of the Fifth Edition. Comments or proposals for revisions on any part of the Standard may be submitted to UL at any time. Proposals should be submitted via a Proposal Request in ULs On-Line Collab
12、orative Standards Development System (CSDS) at http:/. ULs Standards for Safety are copyrighted by UL. Neither a printed nor electronic copy of a Standard should be altered in any way. All of ULs Standards and all copyrights, ownerships, and rights regarding those Standards shall remain the sole and
13、 exclusive property of UL. COPYRIGHT 2012 UNDERWRITERS LABORATORIES INC. ANSI/UL 1567-2012UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL MARCH 16, 2012 UL 1567 2 No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODU
14、CTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL CONTENTS INTRODUCTION 1 Scope .4 2 Components 4 3 Units of Measurement .4 4 References .5 PERFORMANCE 5 General 5 6 Heat Cycling .9 7 Vibration 11 8 Thermal and Humidity Exposure .13 9 Terminal Tightening Withstand 14 MARCH 16, 2012 UL 1567 3UL COPYRI
15、GHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL INTRODUCTION 1 Scope 1.1 These requirements cover wire binding screw terminals of receptacles and switches rated 15 or 20 A intended for use with solid conductor aluminum building wire, and that require
16、 direct connection of wiring conductor(s) to the binding head screw terminal(s) prior to insertion of the device in an outlet box. 1.2 These performance requirements for wire binding screw terminals are in addition to the requirements for the products covered by the Standard for Attachment Plugs and
17、 Receptacles, UL 498, and the Standard for General-Use Snap Switches, UL 20. 2 Components 2.1 Except as indicated in 2.2, a component of a product covered by this Standard shall comply with the requirements for that component. 2.2 A component need not comply with a specic requirement that: a) Involv
18、es a feature or characteristic not needed in the application of the component in the product covered by this Standard, or b) Is superseded by a requirement in this Standard. 2.3 A component shall be used in accordance with its recognized rating established for the intended conditions of use. 2.4 Spe
19、cic components are recognized as being incomplete in construction features or restricted in performance capabilities. Such components are intended for use only under limited conditions, such as certain temperatures not exceeding specied limits and shall be restricted to use only under those specic c
20、onditions for which they have been recognized. 3 Units of Measurement 3.1 Values stated without parentheses are the requirement. Values in parentheses are explanatory or approximate information. MARCH 16, 2012 UL 1567 4UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION W
21、ITHOUT PERMISSION FROM UL 4 References 4.1 Any undated reference to a code or standard appearing in the requirements of this Standard shall be interpreted as referring to the latest edition of that code or standard. PERFORMANCE 5 General 5.1 Test Wire Size Products rated 15 or 20 A shall be investig
22、ated for use with 12 (3.3 mm 2 ) and 10 AWG (5.3 mm 2 ) aluminum conductors when they are intended for use on branch circuits protected by overcurrent protection rated either 15 or 20 A in accordance with the National Electrical Code (NEC) ANSI/NFPA-70. Products rated 20 A shall be investigated for
23、use with 10 AWG wire. Products rated 15 A that are not intended for use on a 20-A branch circuit shall be investigated with 12 AWG wire. 5.2 Test Wire Characteristics The aluminum test wire shall be thermoplastic insulated building wire, Type TW or THW. The conductor shall be EC alloy 1350 aluminum
24、having the characteristics indicated in Table 5.1 with an ultimate tensile strength of 17000 21000 lbf/in 2 (117.2 144.8 MPa), a minimum percentage elongation of 7 and a maximum percentage elongation of 10. The test conductor shall be drawn from 3/8 inch (9.5 mm) diameter rod to the nished size with
25、out any intermediate annealing. The conductor shall be batch annealed with air atmosphere to obtain the physical characteristics. Table 5.1 Chemical sample analysis (percentage by weight EC alloy 1350) Element Nominal Minimum Maximum Iron 0.25 0.40 Gallium 0.001 0.014 Silicon 0.03 0.06 Vanadium 0.00
26、2 0.005 Boron 0.004 Sodium 0.012 Aluminum 99.50 Nickel 0.001 Zinc 0.01 Manganese 0.003 Chromium 0.001 Titanium 0.002 Magnesium 0.001 Copper 0.001 5.3 Device Mounting Receptacles and switches are to be mounted with the major axis of the device in a vertical position. The ground pin slot of a receptac
27、le is to be at the top. The devices shall be secured to special test frames in a normal position of mounting, arranged to minimize the transfer of heat from adjacent terminals. The position of the terminal surface shall be vertical so as to permit free air ow across the terminal when consistent with
28、 the normal mounting position. Any specic marked mounting position of the device shall be observed. The devices mounting strap shall be thermally insulated from the test frame to minimize heat transfer from the terminals. (See 6.10). MARCH 16, 2012 UL 1567 5UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR
29、 FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL 5.4 Test Connections The devices are to be connected in a circuit using the appropriate gauge and interconnecting lead lengths specied in the individual tests. 5.5 The test circuit is to be connected to a regulated 60 Hz power supply u
30、sing supply conductors having an ampacity at least that of the test current. 5.6 Where the construction of the product terminals meets the intent of the requirement for through connection, such as a duplex receptacle with two terminal screws per terminal, the product terminals shall be utilized for
31、connection of feed-through conductors. See Figure 5.1. This is generated text for gtxt. 5.7 When the product terminal construction precludes through connection of wiring, such as a switch with a single terminal screw per terminal, the test wires shall be connected to the product such that the produc
32、t performs its normal function. See Figure 5.2 This is generated text for gtxt. Figure 5.1 Wiring for through connection terminal examples MARCH 16, 2012 UL 1567 6UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL 5.8 In order to evaluate a dev
33、ice mentioned in 5.7, modied devices are not prohibited when unrelated variables inuence the test results. For example, in order to obtain a through connection, switch contacts and internal current carrying parts of a receptacle bonded, jumpered by a soldered 14 AWG (2.1 mm 2 ) copper wire or equiva
34、lent means, meet the intent of the requirement. Modications are not to provide any increase in overall thermal or electrical conductivity, mechanical strength and so forth, beyond that of the basic unmodied device construction. 5.9 The end of the aluminum test wires to be connected to the device wir
35、e binding screws shall be formed in a plane to have a 180 degree bend. The inside diameter of the bend shall be equal to 0.02 inch (0.5 mm) more than the nominal diameter of the device terminal screw. The end of the conductor shall not project from under the head of the screw more than approximately
36、 1/2 of the diameter of the test conductor. A conductor forming jig shall be used to facilitate wiring in a reproducible fashion (see Figure 5.3). This is generated text for gtxt. Figure 5.2 Wiring for single screw terminal examples MARCH 16, 2012 UL 1567 7UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR
37、FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL 5.10 The insulation of the test wire shall be removed in order to expose 1/4 inch (6.4 mm) of conductor beyond the head of the binding screw. Exception: When the device incorporates provisions, such as wire guides or channels, intended
38、to minimize the transmission of wire bending forces to the terminals, as in the case of a device that is wired and then moved into place, the length of the exposed conductor beyond that necessary to make the connection shall be selected so as to result in the least favorable test condition for the w
39、ire disturbance test. For example, a wire guide intended to accept an insulated conductor is to be tested with the wire insulation stripped back beyond the wire guide, and a wire guide intended to accept a 12 (3.3 mm 2 ) and a 10 AWG (5.3 mm 2 ) uninsulated conductor is to be tested with the 12 AWG
40、(3.3 mm 2 ) conductor wire insulation not removed in the area of the guide when the guide accepts the insulated conductor. 5.11 Temperature Measurements Those parts of the test program that require measurement of the terminal temperatures generated by current ow through the device shall be conducted
41、 in a substantially draft-free location. The room ambient temperature shall be maintained between 20 and 35C (68 and 95F). 5.12 Temperatures shall be measured using thermocouples as described in 5.14 and an appropriate indicating instrument. A potentiometer type of indicating instrument is to be use
42、d whenever referee temperature measurements are required. Thermocouples shall be placed close to the point of maximum heating of the terminal. Figure 5.3 Forming test conductor MARCH 16, 2012 UL 1567 8UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION
43、FROM UL 5.13 In applying 5.12, exploratory tests to determine the accessible point where maximum heating occurs are not prohibited. Thermocouples are to be located so as not to interfere with any wire disturbance test. On devices that meet the intent of the requirement for through connections, the t
44、hermocouple is to be placed on the break-off strap (if provided) or between the terminal screws of a solid plate. When the terminal plate is recessed or otherwise inaccessible, placing the thermocouple on the terminal screw or conductor, whichever results in the highest temperature rise, meets the i
45、ntent of the requirement. 5.14 Thermocouples are to consist of 30 AWG (0.05 mm 2 ) iron and constantan wire. The thermocouple wire shall conform with the requirements specied in the Tolerances on Initial Values of EMF versus Temperature tables in the Standard Specication and Temperature-Electromotiv
46、e Force (emf) Tables for Standardized Thermocouples, ANSI/ASTM E230/E230M. 5.15 All temperature measurements shall be made after thermal equilibrium has been achieved. Thermal equilibrium occurs within the rst 2-3/4 hours of the 3-1/2 hour on part of the heat cycle. The ambient temperature shall be
47、measured in the immediate vicinity of the device under test at a point that is not affected by the heat from the device and its wiring. 6 Heat Cycling 6.1 A wire binding screw terminal shall be subject to a heat cycling test. Twenty-four wire binding screw terminal connections shall be tested: a) Us
48、ing 10 AWG (5.3 mm 2 ) test wire with a test current of 53 A for device terminals rated 20 A. b) Using 12 AWG (3.3 mm 2 ) test wire with a test current of 40 A for device terminals rated 15 A. Exception: When a product terminal rated 15 A is such that it is also capable of being connected to a 20 A
49、branch circuit, as in a duplex receptacle, a second set of 24 terminal connections shall be tested using 10 AWG (5.3 mm 2 ) test wire at 53 A. 6.2 The test current through the terminals shall be cycled 3-1/2 hours on and 1/2 hour off for 500 cycles. The temperature rise at any time during the heat cycling on a terminal shall not exceed 100C (180F) and the stability factor (see 6.7) shall not exceed 10 (18 when temperatures are mea